Enviro C-11278 Kit Components, Initial Installation, Qualified Installers Only, Qnty, Description

Models: 50-645 C-10078 C-11278

1 42
Download 42 pages 28.95 Kb
Page 18
Image 18
Fireplace Horizontal Vent Kit 50-1235:

Initial Installation

QUALIFIED INSTALLERS ONLY

Table 2: Vent termination clearances, refer to Figure 24.

Letter

Canadian Installation 1

US Installation2

Description

A

12 in (30 cm)

Clearance above grade, verandah, porch, deck, or balcony.

 

 

 

 

B

12 in (30 cm)

9 in (23 cm)

Clearance from window or door that may be opened.

 

 

 

 

C

12 in (30 cm)*

Clearance from permanently closed window (to prevent

 

 

 

condensation).

 

 

 

D

24 in (60 cm)*

Vertical clearance to ventilated soffit located above the

 

 

 

terminal, within a horizontal distance of 2 ft (60 cm) from

 

 

 

center line of terminal.

 

 

 

E

18 in (45 cm)*

Clearance to unventilated soffit.

 

 

 

F

12 in (30 cm)*

Clearance to outside corner.

 

 

 

G

12 in (30 cm)*

Clearance to inside corner.

 

 

 

 

H

3 ft (91 cm) within a height of

3 ft (91 cm) within a height of

Clearance to each side of center line extended above

 

15 ft (4.5 m) above the meter/

15 ft (4.5 m) above the meter/

meter/regulator assembly.

 

regulator assembly

regulator assembly*

 

 

 

 

 

I

3 ft (91 cm)

3 ft (91 cm)*

Radial clearance around service regulator vent outlet.

 

 

 

 

J

12 in (30 cm)

9 in (23 cm)

Clearance to non-mechanical air supply inlet to building, or

 

 

 

the combustion air inlet to any other appliance.

 

 

 

 

K

6 ft (1.83 m)

3 ft (91 cm) above if within 10

Clearance to mechanical air supply inlet.

 

 

ft (3 m) horizontally

 

 

 

 

 

L

7 ft (2.13 m)t

7 ft (2.13 m)*t

Clearance above paved sidewalk or paved driveway located

 

 

 

on public property.

 

 

 

 

M

12 in / 30 cm+

12 in / 30 cm*+

Clearance under verandah, porch, deck, or balcony.

N

12 in (30 cm)*

Clearance horizontally to any surface (such as an exterior

 

 

 

wall) for vertical terminations.

 

 

 

O

12 in (30 cm)

Clearance above roof line for vertical terminations.

 

 

 

 

1In accordance with the current CSA B149, Natural Gas and Propane Installation Code.

2 In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.

* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier.

t A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings. + Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

NOTE: Venting terminals shall not be recessed into walls or siding.

Fireplace Horizontal Vent Kit 50-1235:

Please read and understand these instructions before installing. Failure to follow these instructions carefully could cause property damage or personal injury.

KIT COMPONENTS:

Qnty

Description

Qnty

Description

 

 

 

 

1

Horizontal direct vent termination cap

4

Wire spacers

 

 

 

 

1

Flue collar adapter

1

4 oz tube Mill-Pac Sealant

 

 

 

 

1

Wall thimble

1

4 oz tube RTV silicone

 

 

 

 

 

1

5’

(190 cm) length of Ø4” (10 cm) double walled flex pipe

12

9/16” tech screws

1

5’

(190 cm) length of Ø6⅝” (16.8 cm) double walled flex pipe

8

1½” wood screws

 

 

 

 

 

Please ensure that all components are supplied with this kit. If components are missing or have been damaged, contact your dealer, distributor, or courier company. Do not attempt the installation if components are missing or damaged.

18

Page 18
Image 18
Enviro C-11278 Kit Components, Initial Installation, Qualified Installers Only, Fireplace Horizontal Vent Kit, Qnty