Enviro C-11278, C-10078 Initial Installation, Qualified Installers Only, Use of Wall Straps

Models: 50-645 C-10078 C-11278

1 42
Download 42 pages 28.95 Kb
Page 27
Image 27
Figure 35: Use of Wall Straps.

Initial Installation

QUALIFIED INSTALLERS ONLY

NOTES:

(1)If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet (914 mm), to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (see Figure 35).

(2)When ever possible, use 45° degree elbows instead of 90° degree elbows. The 45° degree elbow offers less restriction to the flow of flue gases and intake air.

(3)For multi story installations; a ceiling firestop is required at the second floor, and any subsequent floors (see Figure 29). The opening should be framed to 10” (254 mm) x 10” (254 mm) inside dimensions, in the same manner as shown in Figure 36.

Figure 35: Use of Wall Straps.

(4)Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passes through, must be enclosed. The enclosure may be framed and sheet-rocked with standard building materials. However consult the appliance manufactures installation instructions for the minimum allowable clearance between the outside of the vent pipe, and the combustible surfaces of the enclosure. Do not fill any required air spaces with insulation.

Figure 36: Multi-Story Vent Pipe Installation.

27

Page 27
Image 27
Enviro C-11278 Initial Installation, Qualified Installers Only, Use of Wall Straps, Multi-StoryVent Pipe Installation