CLEARANCES TO COMBUSTIBLES - FREESTANDING:
When installing this unit on a combustible floor (for example linoleum, hardwood flooring) a non- combustible hearth pad must be under the unit. The pad must extend at least the width of the appliance [22” (558 mm)] and at least the depth of the appliance plus 6” (153 mm) in front of the appliance [29 3⁄4” (756 mm)].
Side wall to unit | - 6 inches | (15 cm) |
Back wall to unit | - 1 inches | (2.5 cm) |
Corner to unit | - 1 inches | (2.5 cm) |
Door front to edge of floor protection | ||
| - 6 inches | (15 cm) |
36" |
(91cm) |
30" |
(76 cm) |
48" |
(122 cm) |
Figure 9: EF2 Freestanding Minimum Alcove Size.
These dimensions are minimum clearances but it is recommended that you ensure sufficient room for servicing, routine cleaning and maintenance.
| ���� ���� |
|
| �� | �� |
| ��� ��� | |
| ��� ��� | |
���� | �� |
|
���� |
| |
���� ��� |
| |
|
| |
| �� |
|
| ���� ��� |
|
| ����� ���������� |
|
Figure 8: EF2 Freestanding Clearance to Combustibles.
Minimum Alcove width | - 36 inches | (91 cm) |
Minimum Alcove height | - 48 inches | (122 cm) |
Minimum Alcove depth | - 30 inches | (76 cm) |
CLEARANCES TO COMBUSTIBLES - FIREPLACE INSERT:
Refer to Figure 10. |
|
|
Side wall to unit | - 8 inches | (20.3 cm) |
Mantel projection | - 10 inches | (25.4 cm) |
Mantel to top of unit | - 8 inches | (20.3 cm) |
Top facing to unit | - 8 inches | (20.3 cm) |
Side facing to unit | - 6 inches | (15.2 cm) |
Floor protection | - 6 inches | (15.2 cm) |
on either side and to the front must
be protected by
| 10" (25.4 cm) Mantel | |
| 8" | |
| (20.3 cm) | |
Wall | 8" | |
Side | ||
(20.3 cm) | ||
| ||
Floor Protection; Minimum 6" (15 cm) in front of door |
Figure 10: EF2 Fireplace Insert Clearance to Combustibles.