Programming Door Run Times
In this stage, your control board will memorize where your limits are (identified by limit switches, positive stops or both) in both opening and closing phases. Also if the
FOR SAFETY
1.Release the operator gears using the manual release process. Once released, manually move the doors half way between the open and close stop points.
2.Relock the operator gears at the half way point through its cycle. Verify your operator control
board is showing on the LED
display.
3.Press and hold down P2 until the LED display shows the A parameter and the relevant number appear in the LED display.
4.Give an OPEN A command. This can be done with any
opening device (keypad, push button, etc…) wired into OPEN A and COM or using the transmitter. You can also briefly (one second or less) jump OPEN A and COM with a wire. This will begin your doors in the
CLOSING DIRECTION and the LED display will read “Pr”.
IMPORTANT: If the doors begin to open rather than close, the doors must be stopped with a reset pulse.
You can either:
Touch the TWO pins of the JMP “RESET” using a screwdriver OR
Disconnect all power (transformer and backup battery)
5.4
Then switch the wires leading into