LED Lights & Operational Displays
Control Board LED Lights - The control board LED lights are located above their respective terminals that they represent. (With exception of ALIM, power supply light, which is located below the power terminals in the upper left corner.) The LED lights are a quick way of verifying necessary connections are made. Below is a chart of their interpretations.
LED | ON | OFF |
|
|
|
ALIM | Powers supply by transformer | Power supply by battery or no power |
|
|
|
FCC 1 | Motor 1 closing limit switch - not tripped | Motor 1 closing limit switch - tripped |
|
|
|
FCA 1 | Motor 1 opening limit switch - not tripped | Motor 1 opening limit switch - tripped |
|
|
|
FCC 2 | Motor 2 closing limit switch - not tripped | Motor 2 closing limit switch - tripped |
|
|
|
FCA2 | Motor 2 opening limit switch - not tripped | Motor 2 opening limit switch - tripped |
|
|
|
STOP | Stop command - not activated | Stop command - activated |
|
|
|
FSW CL | Closing safety device - not tripped | Closing safety device - tripped |
|
|
|
FSW OP | Opening safety device - not tripped | Opening safety device - tripped |
|
|
|
During idle for single door openers, all should be on except FCC 2 and FCA 2. During idle for dual door openers, all LED lights should be on.
If not using safety devices , you must jump STOP, FSW CL and FSW OP to COM in order for the door opener to function.
Standard Operation Display - This is when the door opener is not in parameter setting mode or programming mode. LED displays DS1 and DS2 will show the following:
Door Status
Door At Rest in Closed Position
Door Opening or Door Open when Auto Close is OFF
Door open in pause status
(Only with automatic
Door Closing | 6.1 |
|