Standard Dry Contact Interface Card (Novell style)
Please refer to the following schematic for interface details:
JP1 | J1 |
JP2 | J2 |
JP3 | J3 |
|
| PIN & JUMPER ASSIGNMENT FOR THE FALCON | |
|
| UA88374 RELAY OPTION BOARD | |
|
| (no | |
| PIN | DESCRIPTION |
|
| 1 | Low Battery ( When UPS reaches low battery, contact activates) |
|
|
| (J1, |
|
| 2 | JP2 shorted = Low Battery common & all other shorted JP commons |
|
|
| JP2 open = common for low battery only |
|
| 3 | Utility Loss N.O. ( At loss of utility voltage, contact activates) |
|
| 4 | Utility Loss N.C. ( At loss of utility voltage, contact activates) |
|
| 5 | JP1 shorted = Utility Loss common & all other shorted JP commons |
|
|
| JP1 open = Utility Loss common only |
|
| 6 | Remote Shutdown common |
|
| 7 | Remote Shutdown |
|
|
| (J2, |
|
|
|
| |
|
| and seven, while the UPS is on battery, will turn the UPS off. |
|
|
|
| |
|
| seven, while the UPS is on battery, will turn the UPS off. |
|
| 8 | Alarm (Upon a UPS fault or failure the contact activates) |
|
|
| (J3, |
|
| 9 | JP3 shorted = Alarm common & all other shorted JP commons |
|
|
| JP3 open = Alarm common only |
|
|
| PIN & JUMPER ASSIGNMENT FOR THE FALCON | |
|
| UA88376 RELAY OPTION BOARD | |
|
| (with | |
|
|
| |
|
| ||
| PIN | DESCRIPTION | |
| 1 | Low Battery ( When UPS reaches low battery, contact activates) | |
|
| (J1, | |
| 2 | JP2 shorted = Low Battery common & all other shorted JP commons | |
|
| JP2 open = common for low battery only | |
| 3 | Utility Loss N.O. ( At loss of utility voltage, contact activates) | |
| 4 | Utility Loss N.C. ( At loss of utility voltage, contact activates) | |
| 5 | JP1 shorted = Utility Loss common & all other shorted JP commons | |
|
| JP1 open = Utility Loss common only | |
| 6 | Remote Shutdown common | |
| 7 | Remote Shutdown | |
|
| (J2, | |
|
| ||
|
| and seven, while the UPS is on battery, will turn the UPS off. | |
|
| ||
|
| seven, while the UPS is on battery, will turn the UPS off. | |
| 8 | On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure | |
|
| the contact activates) | |
|
| (J3, | |
| 9 | JP3 shorted = On bypass, Alarm common & all other shorted JP | |
|
| commons | |
|
| JP3 open = On bypass, Alarm common only |
21