Qty x V x Rating Pack
4 x 12 V x 7.2 AH
ENVIRONMENTAL |
|
Operating Temperature | +32oF to +104oF (0oC to +40oC) |
Storage Temperature | +5oF to +122oF |
Relative Humidity | 0% to 95%, |
Operating Elevation | Up to 10,000 ft (3000m) at 104oF without |
Audible Noise | <45 dbA, at 1 meter from rear |
AGENCY |
|
Safety | UL 1778, UL Listed |
RFI/EMI | FCC Part 15, Subpart B, Class B |
Surge Immunity | IEC |
Transportation | ISTA Procedure 1A |
COMMUNICATIONS |
|
Serial Port | |
Slot | Option for SNMP, USB card or DB 9 card |
SOFTWARE |
|
UPSILON | Supplied bundled to support Windows 95, 98, |
| NT, ME, 2000, XP |
BATTERY RUN TIMES
RUN TIME CHART in Minutes
| UPS | 800VA | 1000VA | 1500VA | 2000VA | 3000VA |
| Model | (560W) | (700W) | (1050W) | (1400W) | (2100W) |
13 | 9 | 5 |
|
| ||
+ 1 Battery Module | 62 | 53 | 31 |
|
| |
+ 2 Battery Modules | 131 | 96 | 60 |
|
| |
+ 3 Battery Modules | 193 | 154 | 92 |
|
| |
|
|
|
|
| ||
+ 1 Battery Module | 40 | 27 | 16 | 11 |
| |
+ 2 Battery Modules | 89 | 65 | 47 | 30 |
| |
+ 3 | Battery Modules | 159 | 121 | 68 | 56 |
|
|
|
|
|
|
| |
+ 1 | Battery Module | 38 | 26 | 15 | 10 | 5 |
+ 2 | Battery Modules | 86 | 63 | 46 | 29 | 16 |
+ 3 | Battery Modules | 153 | 118 | 67 | 54 | 31 |
NOTE:
1.Approximate discharge time is in minutes and at 77oF (25oC) with a 100% resistive load.
2.For extended battery modules please order them from Falcon Electric Sales.
30