1 box contains:

2 boxes contain:

 

Box 1:

UPS module with fitted battery pack

UPS module without battery

RS-232 cable

RS-232 Cable

Software CD

Software CD

Manual

Manual

19” rack ears (+ screws)

19” rack ears (+ screws)

Tower Mounting feet

Tower Mounting feet

 

Box 2:

 

Battery Module

 

Battery connection cable

 

Keyhole hardware

 

19” rack ears (+ screws)

 

1 set of mounting plates

INSPECTING THE EQUIPMENT

 

Visually inspect the UPS for freight damage. If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier, and immediately file a claim for shipping damage with the carrier. If you discover damage after acceptance, file a claim for concealed damage.

To file a claim for shipping damage or concealed damage:

1.YOU MUST file with the carrier within 15 days of receipt of the equipment;

2.YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.

CAUTION

The UPS and Battery Module are heavy. Take proper precautions when lifting or moving them.

Install the UPS indoors in a controlled environment; place it in an area with unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a minimum clearance of 4 inches in the front and rear of the UPS. Maintain an ambient temperature range of 32oF to 104oF (0oC to 40oC). To maximize the life time of the batteries, an ambient temperature of 68oF to 77oF (20oC to 25oC) is recommended. OPERATION IN TEMPERATURES ABOVE 77OF (25OC) WILL REDUCE BATTERY LIFE.

The XG Series UPS can be installed in either a free-standing mini-tower or into a 19 inch equipment rack. Follow the appropriate instructions in either RACK-MOUNT UPS SETUP or

FREE-STANDING UPS INSTALLATION.

RACK-MOUNT UPS SETUP

All XP Series UPSs are shipped with front panel mounting ears that allows the unit to be installed in a 19” rack. Each UPS unit and external battery enclosure needs 2U of rack space.