FS-8700-112 FCI 7100 Series Driver Manual

Page 18 of 24

Appendix A.4. Panel Synchronization

Manual synchronization is required. Push the reset button on the panel. This transmits a reset message to the FieldServer, which clears the data in the FieldServer. After a reset the panel sends messages to report all abnormal states. When all these messages have been processed the FieldServer and panel will be synchronized. This process can be repeated at any time.

Appendix A.5. What happens when the panel sends a Reset Message

When a panel sends a reset message the driver processes every single Map Descriptor, looking at the ‘Clear on Reset’ parameter (See section 4.4.2). If the parameter is set to yes, then the driver sets all the Data Array elements referenced by the Map Descriptor to zero by looking up the DA Name, the Data Array offset and the length. The driver also clears the relevant sections of a Data Array specified with the DA_Bit_Name parameter.

The process can take some time. For this reason, it is suggested that you take care not to set MD length to a value larger than necessary.

Additional considerations apply when panels are connected together in an FCI network. See section ??????????????

Appendix A.6. Networked Panels.

The driver can processes messages and store data from multiple panels provided that:

The panels are connected in an FCI network and the panels are configured to report their events to the main panel

The main panel is configured to send the node of origin in a message preceding the event message. Consult with FCI for information on how to achieve this.

Example of message sent by a panel that is networked. The driver is dependent on seeing the node of event origin included in parenthesis before each event message.

F.S.E.C.

(Node02):

Thermal Det

L1S02 00:40:18

01/01/99

MISSING:

PROJ MANG OFFICE

F.S.E.C.

(Local):

 

00:40:18

01/01/99

RESET:

 

 

The main panel is identified as ‘(Local)’. The driver interprets this as Node_ID=0.

To capture events from multiple networked panels you need one Node Descriptor for each panel with the appropriate Node_ID. Each node requires a set of Map Descriptors.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 18