FS-8700-112 FCI 7100 Series Driver ManualPage 19 of 24
Appendix B. Driver Error Messages.
Message |
|
|
|
|
| Description |
|
FCI7100:#1 FYI. Use a DA called <%s> to expose | Refer to Appendix B.1 | ||||||
diagnostic info., FCI_7100_STATS_DA ) |
|
|
| ||||
FCI7100:#2 | FYI. Added | Event | Desc=<%s> |
|
| ||
Index=%d | Categ=%d | , | new_event_desc | , | Printed for your info only. No action | ||
new_event_desc_index_value |
| , | required if it confirms your expectations. | ||||
new_event_desc_categ ) ; |
|
|
|
|
| ||
FCI7100:#3 | Err. No space. Reject Event | There is only space for 60 event types.2 | |||||
Desc=<%s> Index=%d , new_event_desc | , | ||||||
new_event_desc_index_value ) ; |
|
|
|
| |||
|
|
|
|
|
| You are adding an event type that | |
FCI7100:#4 FYI. Duplicate Event Desc=<%s>. , | already exists. | If you are updating the | |||||
new_event_desc ) ; |
|
|
|
| category, ignore the message. Otherwise | ||
|
|
|
|
|
| correct the configuration file.2 | |
|
|
|
|
|
| You are adding an event type that | |
FCI7100:#5 FYI. Duplicate Event Desc=<%s>. , | already exists. | If you are updating the | |||||
new_event_desc ) ; |
|
|
|
| index value, ignore the message. | ||
|
|
|
|
|
| Otherwise correct the configuration file.2 | |
FCI7100:#6 Err. Event Index=%d. Too big to set | If the event index is greater than 64 then | ||||||
the data cannot be stored as bits as only | |||||||
bit., |
|
|
| 64 bits are reserved for events. | |||
|
|
|
|
|
| ||
FCI7100:#7a Err. DA=%s too short. Rqd=%d, dt- | The MD in question has a length and | ||||||
>buffer_name , offset ); |
|
|
|
| offset which makes it run past the end of | ||
FCI7100:#7b Err. DA=%s too short. Rqd=%d, | the Data Array. Message 7b is printed | ||||||
| when data is being stored as bits.2 | ||||||
FCI7100:#8 FYI. Reset was rcvd and processed! | Printed for your info only. No action | ||||||
Stamped %s %s , |
| required. |
| ||||
|
|
|
|
|
| This message is printed when a reset | |
FCI7100:#9 Err. Reset was ignored. |
|
| was received but for one or more reason | ||||
|
| the driver could not reset any data. Have | |||||
|
|
|
|
|
| you set 'Clear_on_Reset' to 'no' on all | |
|
|
|
|
|
| MD's ? |
|
FCI7100:#10 FYI. Reset of DA=%s Off=%d |
|
| |||||
Len=%d, | Printed for your info only. No action | ||||||
| , | required.. |
| ||||
|
|
|
|
| |||
FCI7100:#11 Err. Cant reset DA=%s len=%d |
|
| |||||
rqd=%d, | , | The MD in question has a length and | |||||
da_get_length_in_items |
| ( | (DAH_TYP) | offset which makes it run past the end of | |||
) | , | possible_md- | the Data Array.2 |
| |||
>data_length+possible_md- |
|
|
|
|
| ||
>bxi_data_buffer_offset ); |
|
|
|
|
|
2Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.