FieldServer FS-8700-112 Client Side Connection Descriptions, Page 8 of, Section Title, Function

Models: FCI 7100 Series FS-8700-112

1 24
Download 24 pages 19.37 Kb
Page 8
Image 8
Page 8 of 24

FS-8700-112 FCI 7100 Series Driver Manual

Page 8 of 24

4.2.Client Side Connection Descriptions

 

Section Title

 

 

 

 

Connections

 

 

 

 

Column Title

Function

 

Legal Values

 

Port

Specify which port the device

is

P1-P8, R1-R21

 

 

connected to the FieldServer

 

 

 

Protocol

Specify protocol used

 

FCI_7100, FCI_7100_series,

 

 

FCI7100

 

 

 

 

 

Baud*

Specify baud rate

 

1200 – Vendor Limitation

 

Parity*

Specify parity

 

None – Vendor Limitation.

 

Data_Bits*

Specify data bits

 

8 – Vendor Limitation

 

Stop_Bits*

Specify stop bits

 

1 – Vendor Limitation

 

Handshaking*

The 7100 series panels do not support hand

shaking.

 

Poll _Delay*

This commonly used parameter has no meaning for this driver.

Example

//Client Side Connections

Connections

Port,

Protocol,

Baud,

Parity

P8,

FCI_7100,

1200

None

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.