FieldServer Page 21 of, FS-8700-112 FCI 7100 Series Driver Manual, Message, Description

Models: FCI 7100 Series FS-8700-112

1 24
Download 24 pages 19.37 Kb
Page 21
Image 21
Page 21 of 24

FS-8700-112 FCI 7100 Series Driver Manual

 

Page 21 of 24

 

 

 

 

 

 

 

 

 

 

 

Message

 

 

 

Description

 

 

 

FCI7100:#28

Err. Invalid Sensor

number.

 

 

 

 

 

Expected 1..99

 

 

 

 

 

 

FCI7100:#29 Err. Invalid Zone number. Expected

 

Correct the configuration file. 4

 

 

1..255

 

 

 

 

 

 

 

FCI7100:#30 Err. Invalid Relay number. Expected

 

 

 

 

1..255

 

 

 

 

 

 

 

FCI7100:#31 Err. Point Type Invalid.

 

 

Valid Point Types are listed in Section

 

 

 

 

4.4.24

 

 

 

FCI7100:#32 Err. No MD Length. Default to 1

 

You must specify the 'length' of each Map

 

 

 

 

Descriptor. Refer to Section 4.4.244

 

 

 

 

 

 

 

The driver can only listen passively for

 

 

 

FCI7100:#33 Err. Driver cant poll or write.

 

 

message from the panel. Remove any

 

 

 

 

 

active Map Descriptors from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

configuration file.

 

 

 

 

 

 

 

An event message is less than 80 bytes

 

 

 

FCI7100:#36

Err. Too Short. Bytes=%d

, conn-

 

long. If this error is repeated often it is

 

 

 

>ux_iptr"

 

 

 

possible that a FCI firmware update as

 

 

 

 

 

 

made the driver unusable. Take a log and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact tech support.

 

4Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 21
Image 21
FieldServer instruction manual Page 21 of, FS-8700-112 FCI 7100 Series Driver Manual, Message, Description