FieldServer FS-8700-112, FCI 7100 Series Appendix B.1. Driver Stats Exposed, Page 22 of

Models: FCI 7100 Series FS-8700-112

1 24
Download 24 pages 19.37 Kb
Page 22
Image 22
Page 22 of 24

FS-8700-112 FCI 7100 Series Driver Manual

Page 22 of 24

Appendix B.1. Driver Stats Exposed.

In addition to the standard FieldServer operating statistics the driver exposes certain key stats in a Data Array if required. An upstream device can then monitor these stats.

Add the following to your configuration file to activate these stats.

// Expose Driver Operating Stats.

Data_Arrays

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

fci-7100-stats,

UINT32,

200

The driver exposes stats based on a port handle. The offset specified in the table below must be added to the handle number multiplied by 100. i.e. for port whose handle is 1 then the driver will store the 1st stat at 1+100*1=101.

Stat

#define FCI_7100_STAT_NO_PLACE_TO_STORE

#define

FCI_7100_STAT_NO_PLACE_TO_STORE_ZONE

#define

FCI_7100_STAT_NO_PLACE_TO_STORE_RELAY

#define

FCI_7100_STAT_NO_PLACE_TO_STORE_LOOP

#define

FCI_7100_STAT_NO_PLACE_TO_STORE_SENSOR

#define

FCI_7100_STAT_NO_PLACE_TO_STORE_MODULE

#define FCI_7100_STAT_EMPTY_MSG

#define FCI_7100_STAT_SHORT_MSG

#define FCI_7100_STAT_NO_RESET

#define

FCI_7100_STAT_NO_PLACE_TO_STORE_PANEL

#define FCI_7100_STAT_RCVD_MSGS

Offset

1

2

3

4

5

6

7

8

9

10

11

Description

Increments each time point data is received but there is no Map Descriptor to store the data (any)

Increments each time point data is received but there is no Map Descriptor to store Zone data

Increments each time point data is received but there is no Map Descriptor to store Relay data

Increments each time point data is received but there is no MD to store the Loop data

Increments each time point data is received but there is no MD to store the Sensor data

Increments each time point data is received but there is no MD to store the Module data

Number of times that a message line was was zero bytes long (excluding the terminator)

Number of times that a message line was was too short probably a system id tag line

Increments each time a reset was rcvd but no DA was reset

Increments each time point data is received but there is no MD to store data that cannot be attributed to a zone, relay, loop, sensor, module

Increments each time a message is received

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 22
Image 22
FieldServer instruction manual Appendix B.1. Driver Stats Exposed, Page 22 of, FS-8700-112 FCI 7100 Series Driver Manual