| Page 18 of 22 |
|
|
System Trouble | Address |
LOOP CONTINUITY TEST FAIL LOOP 3 | 231 |
LOOP CONTINUITY TEST FAIL LOOP 4 | 232 |
LOOP CONTINUITY TEST FAIL LOOP 5 | 233 |
LOOP CONTINUITY TEST FAIL LOOP 6 | 234 |
LOOP CONTINUITY TEST FAIL LOOP 7 | 235 |
LOOP CONTINUITY TEST FAIL LOOP 8 | 236 |
LOOP CONTINUITY TEST FAIL LOOP 9 | 237 |
LOOP CONTINUITY TEST FAIL LOOP 10 | 238 |
AMP FAIL | 239 |
AC FAIL | 240 |
SCB ASSEM. COM. VERIFIED FAILED | 241 |
8255 PORT CHIP CONTROL WORD CHECK FAILE | 242 |
NETWORK COMMUNICATION LINK FAIL PORT A | 243 |
NETWORK COMMUNICATION LINK FAIL PORT B | 244 |
STYLE 4 SHORT A L1 | 245 |
STYLE 4 SHORT B L1 | 246 |
STYLE 4 SHORT A L2 | 247 |
STYLE 4 SHORT B L2 | 248 |
STYLE 4 SHORT A L3 | 249 |
STYLE 4 SHORT B L3 | 250 |
STYLE 4 SHORT A L4 | 251 |
STYLE 4 SHORT B L4 | 252 |
STYLE 4 SHORT A L5 | 253 |
STYLE 4 SHORT B L5 | 254 |
|
|
System Trouble | Address |
WALK TEST - FIRE PROTECTION IS LIMITED | 485 |
REMOTE PROG MODE ACCESSED | 486 |
DIA PROG. CHANGE DET. SERVICE REQUIRED | 487 |
ISIB DATA MESSAGE RECEIVED ERROR | 488 |
ISIB EXECUTIVE ROUTINE | 489 |
DIB TO SIB CABLE BAD OR MISSING | 490 |
UPLOAD/DOWNLOAD MESSAGE RECEIVED | 491 |
GLOBAL DATABASE MISMATCH | 492 |
SIB PROG. CHANGE DET. SERVICE REQUIRED | 493 |
494 | |
EXCEEDED CONNECTION LIMIT | 495 |
NAM CCBE. PROG LOST | 496 |
MEMORY LOSS | 497 |
DVC COMM LOSS | 498 |
A.C. POWER LOSS. BACK UP ACTIVATED | 499 |
BUZZER | 500 |
PANEL DOOR OPEN | 501 |
OFF NETWORK | 502 |
INSTALL. ERROR | 503 |
OR AUDIO/TELEPHON | 504 |
EXPANDER MODULES | 505 |
MANUAL CONTROL | 506 |
CAT. COMM. FAULT | 507 |
UNKNOWN | 508 |
Appendix A.3. Node Status
•Data for any particular Node is valid while that Node is online and the system is synchronized. Integrity of data for any Node will be lost if the Node goes offline or if synchronism between the FieldServer and the NCA2 Panel is lost.
•Node status offline/online (1/0) is stored in the 502nd address. It is important to read the Node status before reading any information about the Node.
•Node status data integrity itself depends upon system synchronization.
Appendix A.4. FieldServer Synchronization
There is currently no method of
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408)