System Trouble

Address

LOOP CONTINUITY TEST FAIL LOOP 3

231

LOOP CONTINUITY TEST FAIL LOOP 4

232

LOOP CONTINUITY TEST FAIL LOOP 5

233

LOOP CONTINUITY TEST FAIL LOOP 6

234

LOOP CONTINUITY TEST FAIL LOOP 7

235

LOOP CONTINUITY TEST FAIL LOOP 8

236

LOOP CONTINUITY TEST FAIL LOOP 9

237

LOOP CONTINUITY TEST FAIL LOOP 10

238

AMP FAIL

239

AC FAIL

240

SCB ASSEM. COM. VERIFIED FAILED

241

8255 PORT CHIP CONTROL WORD CHECK FAILE

242

NETWORK COMMUNICATION LINK FAIL PORT A

243

NETWORK COMMUNICATION LINK FAIL PORT B

244

STYLE 4 SHORT A L1

245

STYLE 4 SHORT B L1

246

STYLE 4 SHORT A L2

247

STYLE 4 SHORT B L2

248

STYLE 4 SHORT A L3

249

STYLE 4 SHORT B L3

250

STYLE 4 SHORT A L4

251

STYLE 4 SHORT B L4

252

STYLE 4 SHORT A L5

253

STYLE 4 SHORT B L5

254

 

 

System Trouble

Address

WALK TEST - FIRE PROTECTION IS LIMITED

485

REMOTE PROG MODE ACCESSED

486

DIA PROG. CHANGE DET. SERVICE REQUIRED

487

ISIB DATA MESSAGE RECEIVED ERROR

488

ISIB EXECUTIVE ROUTINE RE-ENTERED

489

DIB TO SIB CABLE BAD OR MISSING

490

UPLOAD/DOWNLOAD MESSAGE RECEIVED

491

GLOBAL DATABASE MISMATCH

492

SIB PROG. CHANGE DET. SERVICE REQUIRED

493

HS-NCM SNIFFER MODE ACTIVE

494

EXCEEDED CONNECTION LIMIT

495

NAM CCBE. PROG LOST

496

MEMORY LOSS

497

DVC COMM LOSS

498

A.C. POWER LOSS. BACK UP ACTIVATED

499

BUZZER OFF-LINE

500

PANEL DOOR OPEN

501

OFF NETWORK

502

INSTALL. ERROR

503

OR AUDIO/TELEPHON

504

EXPANDER MODULES

505

MANUAL CONTROL

506

CAT. COMM. FAULT

507

UNKNOWN

508

Appendix A.3. Node Status

Data for any particular Node is valid while that Node is online and the system is synchronized. Integrity of data for any Node will be lost if the Node goes offline or if synchronism between the FieldServer and the NCA2 Panel is lost.

Node status offline/online (1/0) is stored in the 502nd address. It is important to read the Node status before reading any information about the Node.

Node status data integrity itself depends upon system synchronization.

Appendix A.4. FieldServer Synchronization

There is currently no method of auto-synchronizing the FieldServer's Data Arrays with the Notifier NCA2/NFS2- 3030 panel because there is no method for polling the panel through the printer or CRT port. Synchronization of the two devices can be achieved manually pressing the “System Reset” button on the panel while the FieldServer is connected and running. All current events will be re-sent to the FieldServer..

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com