3HARDWARE CONNECTIONS

The FieldServer is connected to the Notifier NCA2/NFS2-3030 Fire Panel as shown in the following connection drawing.

Configure the Notifier Panel according to manufacturer’s instructions.

RJ45

Notifier NCA2/NFS2-3030

Rx (Brown)

Com (Blue/White)

Tx (Orange/White)

Connection to TB5 Printer

Port.

Printer CRT

3HARDWARE CONNECTIONSTB5 PrinterRJ-45Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background TB5

PTX PRX REF CTX CRX REF

FieldServer Part #

8917-16

Pigtail for RJ45

Port

Connect to one of the RS-232

Ports on the FieldServer

FieldServer

8

1

 

P1

Connector Pinouts

TB5 CRT

Function

Receive

Reference

Transmit

 

 

 

 

Pin

CRX

REF

CTX

 

 

 

 

 

 

TB5 Printer

Function

Receive

Reference

Transmit

 

 

 

 

Pin

PRX

REF

PTX

 

 

 

 

 

 

RJ-45

Function

Transmit

Com

Receive

 

 

 

 

Pin

8

4

1

 

 

 

 

 

 

Wire Color

 

Orange/white

Blue/white

Brown

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com