Parameter

 

Addresses

 

 

For each SLC loop per Node

 

 

 

 

 

Memory Type : Detector ; Module

 

 

 

Fire Alarm

 

1 – 159

 

 

 

 

 

 

 

 

Security Life

 

160

– 318

 

 

 

 

 

 

 

 

Life Critical

 

319

– 477

 

 

 

 

 

 

 

 

Medical Emergency

 

478

– 636

 

 

 

 

 

 

 

 

Security Alarm

 

637

– 795

 

 

 

 

 

 

 

 

Critical Process

 

796

– 954

 

 

 

 

 

 

 

 

Supervisory

 

955

- 1113

 

 

 

 

 

 

 

Disabled

 

1114 – 1272

 

 

 

 

 

 

 

Prealarm

 

1273 – 1431

 

 

 

 

 

 

 

Active

 

1432 – 1590

 

 

 

 

 

 

 

ON/OFF

 

1591 – 1749

 

 

 

 

 

 

Memory Type : Detector_Trouble; Module_Trouble

 

 

Troubles/Faults

 

1 – 159

 

 

 

 

 

 

 

Parameter

 

Addresses

 

 

For each Node

 

 

 

 

 

Memory Type : Node_Trouble

 

 

 

Troubles/Faults

 

1 – 508

 

 

 

 

 

 

 

 

Memory Type : Panel

 

 

 

 

 

Panel (Maximum12 Boards and 8 Panel circuits per Board )

 

 

Hardware address

memory address

 

 

Board 1 panel 1

1

 

 

 

 

Board 1 panel 2

2

 

 

 

 

Board 2 panel 1

9

 

 

 

 

-----

 

 

 

 

 

-----

 

 

 

 

 

Board 12 panel 8

96

 

 

 

 

)

 

 

 

 

 

Fire Alarm

 

1 – 96

 

 

 

 

 

 

 

Security Life

 

97 - 192

 

 

 

 

 

 

 

 

Life Critical

 

193

- 288

 

 

 

 

 

 

 

 

Medical Emergency

 

289

- 384

 

 

 

 

 

 

 

 

Security Alarm

 

385

- 480

 

 

 

 

 

 

 

 

Critical Process

 

481

- 576

 

 

 

 

 

 

 

 

Supervisory

 

577

- 672

 

 

 

 

 

 

 

 

Disabled

 

673

- 768

 

 

 

 

 

 

 

 

Prealarm

 

769

- 864

 

 

 

 

 

 

 

 

Active

 

865

- 960

 

 

 

 

 

 

 

 

ON/OFF

 

961

- 1056

 

 

 

 

 

 

 

Memory Type : Panel_Trouble

 

 

 

Troubles/Faults

 

1–96

 

 

 

 

 

 

 

Memory Type : Bell_Trouble

 

 

 

Troubles/Faults

 

1-4

 

 

 

 

 

 

 

Table 1 – Memory Mapping Address