FS-8700-130 Notifier NCA2/NFS-3030 Manual

Page 3 of 22

 

 

1NOTIFIER NCA2/NFS2-3030 DESCRIPTION

The NCA2/NFS2-3030 Serial driver allows the FieldServer to record data from Notifier NCA2 or NFS2-3030 panels over RS-232 as per NFS2-3030/NCA-2EIA-232 Protocol & Data Formats 53219 Rev A 1/3/2008. There is no active polling by this driver; the communications are one-way through the panel's printer or CRT port. The FieldServer acts as a Client; receives messages and records the status of a Panel. The panel MUST output messages in160 characters ASCII format in English.

This driver is not capable of emulating a Notifier NCA2 or NFS2-3030 panel.

The NCA2 controls all the devices (e.g. 3030, 640 panels) connected on the Notifier network. Each Fire Alarm Panel on Network is considered as a Node. 240 Nodes can exist on one network. NFS2-3030 can exist on a network or be self-standing.

NCA2 interacts with other Fire Alarm Panels, records the status of the panels and sends the events to printer and CRT ports. FieldServer captures these events in text form, parses and stores them in Data Arrays. These Data Arrays can be monitored by third party tools. Since the FieldServer does not actively poll for data, the accuracy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues.

If a networked panel does not send the 'CLEARED' message for latched points via the NCA2 it is not possible to detect cleared points unless a system reset is done. It is possible to configure the FieldServer to clear on reset message from NCA2. See Appendix A.4 for more detail.

Please note that the FieldServer can be configured with a large number of points. The point limits purchased with the FieldServer prevent the entire database from being accessed in any one application. It is therefore strongly advisable to ensure that only the point addresses of interest are configured, and that the FieldServer is purchased with the correct point count.

The types of Notifier messages supported by this driver are summarized in Section 4.1. A detailed table presented in Appendix A.1 shows each type of NCA2/NFS2-3030 message the FieldServer recognizes and the effect that it has on the status of the points in the Data Array.

Max Nodes Supported

FieldServer Mode

Nodes

Comments

Client

0

This Driver cannot be used as a Client.

 

 

 

Server

1

Each FieldServer port can connect to only 1 Notifier panel port

 

 

 

2DRIVER SCOPE OF SUPPLY

2.1Supplied by FieldServer Technologies for this driver

 

 

 

 

 

 

 

 

FieldServer Technologies PART #

Description

 

 

 

 

FS-8917-16

Pigtail cable for RJ45 Port

 

 

 

 

 

 

 

 

 

 

FS-8700-130

Driver Manual.

 

 

 

 

 

 

 

 