Appendix A.5. Driver Limitations and Exclusions
•Zone information will not be recorded.
•To synchronize the FieldServer with the panel, connect the running FieldServer and press the “System Reset” button on the panel. All current events will be
•The port must be enabled on the unit and set to 80 columns with NO supervision
•All data related to
•This driver was written as a subset of
•This driver will not record information about zone status that is incorporated with point status messages.
•There can only be one panel connected to any given FieldServer port.
•This driver records data as presented to the printer/CRT port by the Notifier panel, and can only be as accurate as this data.
•The driver cannot send messages to the Notifier panel.
•Driver will clear any data on “System Normal” only if this data is previously set by driver and is not yet cleared by “Cleared” message and is configured to Clear_on_Normal. By default Clear_on_Normal is “yes”.
•Driver will clear any Node data on “System RESET” only if this data is previously set by driver and is not yet cleared by “Cleared” message and is configured to Clear_on_Reset. By default Clear_on_Reset is “no”.