| Page 9 of 22 |
|
|
4.3Client Side Connection Descriptions
Section Title
Connections
Column | Function | Legal Values | |
Title | |||
|
| ||
Port | Specify which port the device is connected to the | ||
FieldServer | |||
|
| ||
|
|
| |
Protocol | Specify protocol used | ||
|
|
| |
|
| CRT Port | |
|
| 4800; 9600; 19200; 38400; 57600; (Vendor | |
Baud* | Specify baud rate | limitation) | |
|
| Printer Port | |
|
| 9600 (Vendor limitation) | |
|
|
| |
Parity* | Specify parity | None (Vendor limitation) | |
|
|
| |
Data_Bits* | Specify data bits | 8 (Vendor limitation) | |
|
|
| |
Stop_Bits* | Specify stop bits | 1 (Vendor limitation) | |
|
|
|
Example |
|
|
| ||
// | Client Side Connections |
| |||
Connections |
|
|
| ||
Port | ,Protocol | ,Baud | ,Stop_Bits | ,Parity | |
P8 |
| ,9600 | ,1 | ,None |
4.4Client Side Node Descriptors
Section Title
Nodes
Column Title | Function | Legal Values | |
Node_Name | Provide name for Node | Up to 32 alphanumeric characters | |
|
|
| |
Node_ID | Station address of any physical Node on | ||
network | 3030 Panel | ||
| |||
|
|
| |
Protocol | Specify protocol used | ||
|
|
| |
Port | Specify which port the device is connected | ||
to the FieldServer | |||
|
| ||
|
|
|
Example |
|
|
| |
// | Client Side Nodes |
|
| |
Nodes |
|
|
| |
Node_Name | ,Node_ID | ,Protocol | ,Port | |
Panel_1 | ,2 | ,P8 |
2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408)