FieldServer FS-8700-41 Hardware Connections, gsdescribedinsection4ofthisdocument

Models: FS-8700-41

1 58
Download 58 pages 34.3 Kb
Page 6
Image 6
3.Hardware Connections

FS-8700-41 Simplex 4100 Driver Manual

Page 6 of 58

3.Hardware Connections

The FieldServer is connected to the Simplex Device’ "COMPUTER", the following port attributes may be co port:

s RS232 port of device type nfigured specifically for that particular

Ensurethatthesesettingscorrespondtothesettin

gsdescribedinsection4ofthisdocument.

Sim4100 Panel

 

 

 

Setting

Default

Options

 

 

BaudRate

9600

75,110,134.5,300,600,1200,1800

,2000,2400,4800,9600,19200

Parity

EVEN 1

ODD,EVEN,MARK,SPACE,NONE

 

DataBits

8

7or8

 

 

StopBits

1

1or2

 

 

Sim4100U Panel

 

 

 

Setting

Default

Options

 

 

BaudRate

9600

75,110,134.5,300,600,1200,1800

,2000,2400,4800,9600,19200

Parity

NONE 1

ODD,EVEN,MARK,SPACE,NONE

 

DataBits

8

7or8

 

 

StopBits

1

1or2

 

 

ThefollowingaretheSimplex,recommendedconnecti onstobeusedincablingbetweenthe 4100andtheFieldServerdevice.Forthecomputer device,thestandardEIAsignaldescription,

andthe25pin(DB25)and9pin(DB9)connectorass ignmentsareshown.

 

 

4100 Host

 

 

 

 

 

 

 

 

 

Computer

 

 

 

 

 

4100

 

 

 

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

Port

Port

 

 

 

Signal

 

 

 

 

Signal

 

 

DB25Pin

 

DB9Pin

 

 

 

DB25 Pin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATB1

BTB2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

1

2

 

 

TXD

RXD

2

2

 

 

 

6

3

3

 

 

RXD

TXD

3

3

 

 

 

7

2

4

 

 

RTS

2

 

RTS

 

4

 

7

 

 

 

 

 

 

 

 

 

 

 

 

5

4

5

 

 

CTS

 

 

 

CTS

5

8

 

 

 

4

5

7

 

 

GND

──

GND

7

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 OddorEvenparityisrecommended(bySimplex)top

rovideadditionalerrordetectionatthecharacter

level.

 

 

 

 

 

2Note,thatifHSHAKEisnotused(SimplexDeviceS

etting),theconnectionsbetweenRTSandCTSare

notrequired

 

 

 

 

 

 

 

FieldServer Technologies1991TarobCourtMilpitas,California95035USA

Web:www.fieldserver.com

Tel:(408)2622299

Fax:(408)2622296