FieldServer FS-8700-41 instruction manual

Models: FS-8700-41

1 58
Download 58 pages 34.3 Kb
Page 36
Image 36
Manual background

FS-8700-41 Simplex 4100 Driver Manual

Page 36 of 58

Appendix A.16. Advanced Map Descriptor Example 7 - Acknowledge a specific point

Theackallfunctioncanbeusedtoackallpointso rallpointsthatareinaparticularstate.Whata boutifyouwishtosendanack messageforasinglepoint.OneMapDescriptorisr equiredforeachcpscombinationyourequirespec ificacknowledgementsfor.

Thedriverchecksthearraylocationcorresponding totheMapDescriptor.Ifthevalueisnonzerothe nanackmessageissent.The

valueisusedtodeterminewhatkindofackissent .Asthefunctioniswrbx,themessageisonlysent whenthevalueisupdated.

Bit0:

F

FireAlarmPanel

Bit1:

P

Priority2alarmstate

Bit2:

T

TroubleState

Bit3:

S

SupervisoryState

Bit4:

U

UtilityMonitor

Bit5:

C

ControlState

Bit6:

D

DisableTroubleState

Bit7:

A

PrimaryPoint

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Length,

Scan_Interval

sim4100_Func

Sim4100_Card,

Sim4100_Point,

Sim4100_Sub

Length

Ack_mapdesc1,

DA_ACK,

0,

Wrbx,

Node_A,

1,

1.0s,

Ack,

1,

2,

3,

1

Ack_Mapdesc2,

DA_ACK,

1,

wrbx,

Node_A,

1,

1.0s,

Ack,

1,

2,

4,

1

 

 

 

 

 

 

 

 

 

 

 

 