4.2.Client Side Connection Descriptions

FS-8700-41 Simplex 4100 Driver Manual

Page 13 of 58

4.2.Client Side Connection Descriptions

 

Section Title

 

 

 

 

Connections

 

 

 

 

Column Title

Function

 

Legal Values

 

Port

Specifywhichportthedeviceisconnected

 

P1P8,R1R2 3

 

 

totheFieldServer

 

 

 

Baud*

Specifybaudrate

 

110–115200,standardbaud

 

 

ratesonly.

 

 

 

 

 

Parity*

Specifyparity

 

Even,Odd,None,Mark,

 

 

Space

 

 

 

 

 

Data_Bits*

Specifydatabits

 

7, 8

 

 

 

 

 

 

Stop_Bits*

Specifystopbits

1

 

 

 

 

 

Protocol

Specifyprotocolused

sim4100

 

 

 

 

 

Handshaking*

Specifyhardwarehandshaking

RTS,RTS/CTS,None

 

PollDelay*

Timebetweeninternalpolls

 

032000seconds, 1 second

 

 

 

 

 

Example

//ClientSideConnections

Connections

Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P8,

Sim4100,

9600,

Even,

None,

0.100s

4.3.Client Side Node Descriptors

SectionTitle

 

 

 

Nodes

 

 

 

ColumnTitle

Function

LegalValues

 

Node_Name

Providenamefornode

Upto32alphanumericcharact

ers

 

 

ThisparameterisIGNORED.Special

Node_ID

Ad

keywordstodefinethecardsubpoint

 

 

aredescribedinsection4.4

 

Protocol

Specifyprotocolused

Sim4100

 

Port

Specifywhichportthedeviceis

P1P8,R1R2 3

 

 

connectedtotheFieldServer

 

 

 

RequiredforSimplex4100Panels.

 

 

 

IfnotspecifiedthenaSimplex

 

 

 

4100/4020panelisassumed.

 

 

PLC_Type*

4020/4100panelswithfirmware

4100,4020,4100U

 

 

version9xorearlier.

 

 

 

4100U–panelswithfirmware

 

 

 

version10xorlater.

 

 

3Notallportsshownarenecessarilysupportedbyt hehardware.ConsulttheappropriateInstruction manualfordetailsoftheportsavailableonspecif ichardware.

FieldServer Technologies1991TarobCourtMilpitas,California95035USA

Web:www.fieldserver.com

Tel:(408)2622299

Fax:(408)2622296

Toll_Free:8885091970

email:support@fieldserver.com