FS-8704-12_GE-EGD Manual

Page 12 of 26

5.Configuring the FieldServer as a GE-EGD Server

5.1.Server Side Connection Descriptors

Section Title

 

 

Connections

 

 

Column Title

Function

Legal Values

Adapter

Adapter Name

N1,N2

Protocol

Specify protocol used

GE_EGD

Example

 

 

 

 

 

Adapters

 

 

Adapter,

Protocol

 

N1,

GE_Egd

 

5.2.Server Side Node Descriptors

 

Section Title

 

 

 

 

 

Nodes

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Node_Name

Provide name for node

Up to 32 alphanumeric

 

characters

 

 

 

 

 

 

Node_ID

This keyword is not required.

 

 

IP_Address

The IP address in dot format

Nnn.nnn.nnn.nnn

 

of the EGD-Device.

 

Where nnn is in the range 0-

 

 

 

255.

 

 

 

 

 

 

Protocol

Specify protocol used

 

GE_Egd

 

 

Specify

which

adapter

 

 

Adapter

connects to the network the

N1, N2

 

 

EGD-device is connected to.

 

 

Example

 

 

 

 

//Producer(Active Server) Side Nodes

Nodes

 

 

 

Node_name,

IP_Address,

Adapter,

Protocol

node_A,

192.168.1.102,

N1,

ge_egd

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 12
Image 12
FieldServer FS-8704-12 instruction manual Server Side Node Descriptors, Section Title