FieldServer FS-8704-12 Appendix B.1. EGD-ii EGD Internal Indications, Array Contents Element

Models: FS-8704-12

1 26
Download 26 pages 48.5 Kb
Page 23
Image 23

FS-8704-12_GE-EGD Manual

Page 23 of 26

Appendix B.1. EGD-ii (EGD Internal Indications)

This driver can expose data from the most recently consumed message and some additional diagnostic information.

A special Map Descriptor is required. The driver recognizes the Map Descriptor by its name which must be "EGD-ii" which stands for EGD Internal Indications.

The following example shows how this special Map Descriptor can be configured.

Nodes

 

 

Node_name,

Protocol

 

null_node,

ge_egd

 

Data_Arrays

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

EGD_DIAG,

UINT32,

100

Map_Descriptors

 

 

Map_Descriptor_Name,

Data_Array_Name,

Node_name

egd-ii,

EGD_DIAG,

null_node

When the driver sees this Map Descriptor it uses the Data Array EGD_DIAG to store driver specific data. Only one of these Map Descriptors may be specified per FieldServer.

The driver stores the following data.

Array

 

Contents

 

Element

 

 

 

 

 

0-31

 

The first 32 bytes of the most recently received UDP packet received on

 

port 0x4746 (The GE EGD port).

 

 

32

PDUTypeVersion

33

RequestID

34

ProducerID2

35

 

ExchangeID

36

TimeStampSec

37

TimeStampNanoSec

38

Status3

39

ConfigSignature

40

Reserved

41

Source IP Address1

2As a UINT32. Not in dot format

3Read section 4.4 of GE-Fanuc document GFK-1541 for more information.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 23
Image 23
FieldServer FS-8704-12 instruction manual Appendix B.1. EGD-ii EGD Internal Indications, Array Contents Element