FieldServer FS-8704-12 instruction manual Dataq

Models: FS-8704-12

1 26
Download 26 pages 48.5 Kb
Page 20
Image 20

 

FS-8704-12_GE-EGD Manual

 

 

 

Page 20 of 26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

node_name,

Length,

ge_producerId,

ge_exchangeId,

ge_data_type,

ge_offset

 

Q1,

DATA_Q,

0

Passive,

PLC90-30,

1,

1.2.3.4,

1,

%q,

0

 

 

R1,

DATA_R,

0

Passive,

PLC90-30,

1,

1.2.3.4,

1,

%r,

1

 

 

I1,

DATA_R,

0

Passive,

PLC90-30,

2,

1.2.3.4,

1,

%u,

3

 

 

R2,

DATA_R,

1

Passive,

PLC90-30,

1,

1.2.3.4,

1,

%r,

5

 

 

I2,

DATA_R,

2

Passive,

PLC90-30,

1,

1.2.3.4,

1,

%i,

7

 

 

Q2,

DATA_R,

1

Passive,

PLC90-30,

1,

1.2.3.4,

1,

%q,

8

 

Read the section on data types to see how many items are being transmitted. Note that the %Q, %I references are actually byte references and not bit references as they are always produced in multiples of 8 and are always byte aligned.

Must correspond to the ‘Local Producer’ in the EGD configuration. Is not necessarily the IP address of the producer port.

These offsets must correspond to the offsets in the EGD configuration.

These data types must correspond to the references in the EGD range configuration.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 20
Image 20
FieldServer FS-8704-12 instruction manual Dataq