FieldServer FS-8704-12 Appendix C.2. Produced Time Stamp, Appendix C.3. Status Values

Models: FS-8704-12

1 26
Download 26 pages 48.5 Kb
Page 25
Image 25

FS-8704-12_GE-EGD Manual

Page 25 of 26

Appendix C. Troubleshooting Tips

Appendix C.1. ProducerID with FieldServer device as Producer

During testing it has been observed that a 90-30 PLC required that the ge_ProducerID parameter was set to the same value as the IP Address of the FieldServer.

Appendix C.2. Produced Time Stamp

The GE-EGD (Ethernet Global Data) driver always set the timestamp of produced data to the time of the Field Server Device. The nanoseconds portion of the time stamp is always set to zero.

Appendix C.3. Status Values

The status of the EGD Exchange may be monitored in the GE PLC. The status value is well documented in GFK-1541 Chapter 4.4. During testing, using the Field Server device as a producer and the GE Device as a consumer the following status values were observed.

0 -> The exchange had never been consumed

1 -> Normal

4 -> Length of produced and consumed exchange not equal - Different messages with the same exchange ID.

6. -> Timeout.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 25
Image 25
FieldServer FS-8704-12 instruction manual Appendix C.2. Produced Time Stamp, Appendix C.3. Status Values