6.6.3.Map Descriptors Example

Only two Map Descriptors are allowed, one to transfer data to the Logix CPU and one to accept data from the Logix CPU.

// Server Side Map Descriptors

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Scan_Interval,

Function,

Node_Name,

IO_Data_Type,

DA_Name_Start4,

DA_Count,

Protocol_Type_ID

Input_BP_Image,

0.2s,

WRBC,

SlotServer_CPU,

REAL,

In_1,

2,

0

Output_BP_Image,

0.2s,

RDBC,

SlotServer_CPU,

REAL,

Out_1,

2,

0

 

 

 

 

 

 

 

 

The following Data Arrays section must exist for the above Map Descriptors:

// Data Arrays

 

 

Data_Arrays

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

In_1,

Float,

76

In_2,

Float,

76

Out_1,

Float,

76

Out_2,

Float,

76

 

 

 

The data format should be chosen to allow no loss of resolution with the chosen IO_Data_Type of the Map Descriptor, e.g. don’t use integer here if you intend transferring float data.

See the Data Arrays section for the maximum Data Array lengths allowed per IO_Data_Type chosen on the Map Descriptor.

4Refer to Appendix A.6 for information specific to naming Logics driver Data Arrays.