FieldServer FS-RA-CLX-BAS Multiple Input Data Arrays, Accessing Multiple Output Data Arrays

Models: FS-RA-CLX-BAS

1 34
Download 34 pages 58.58 Kb
Page 21
Image 21

FS-RA-CLX_SlotServer_Instruction_Manual_(T17011)

Page 21 of 34

8.Programming the ControlLogix CPU for larger SlotServer Interfaces

The previous example is for accessing only one Data Array. The following steps describe how to access multiple Data Arrays.

8.1.Multiple Input Data Arrays

In this example, we access Input Data Arrays In[1] up to In[24]. We simply add to the existing ladder program as shown in the Quickstart example. Add a branch after the CPS element that copies the input image Tag and copy and paste EQU and CPS elements from the first rung. Create a new Input Tag for Lon_In_02 of type REAL and dimension 76. Finally, remember to set the EQU Source B value to 2 to compare for incoming data from the 2nd LonWorks functional block which is In[1].

See the ladder program below how to add In[1].

Very Important Note!

It is very important to first make a synchronous copy of the input image data before using it. If this is not done, the input data cannot be guaranteed to be from a specific LonWorks Function Block.

8.2.Accessing Multiple Output Data Arrays

To access more output Data Arrays is slightly more complicated since we need to create a Multiplexer in Ladder.

The basic steps include:

Create a Counter which counts up every 100ms.

Place the counter value into the Lon_Out_xx Tag at offset 2.

Copy and the whole Tag into the output Data Image Tag for transferring to the LonWorks network.

The example program below shows an output counter that can count up to 25 which allows the transfer of data into 25 Output Function Blocks. Only 2 rungs are shown to transfer data for blocks 1 and 2. Add more rungs with more Lon_Out_xx tags to transfer data to other output Function Blocks.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 21
Image 21
FieldServer FS-RA-CLX-BAS instruction manual Multiple Input Data Arrays, Accessing Multiple Output Data Arrays

FS-RA-CLX-BAS specifications

The FieldServer FS-RA-CLX-BAS is a robust communication gateway designed to facilitate interoperability between building automation systems and various network protocols. Its main objective is to provide seamless integration, allowing different systems to communicate effectively, regardless of their underlying technologies.

One of the standout features of the FS-RA-CLX-BAS is its support for a wide range of communication protocols. It can easily bridge between BACnet, Modbus, Johnson Controls N2, and several others, making it an invaluable tool in diverse environments where equipment from multiple manufacturers needs to work together. This extensive compatibility helps streamline operations, reduce costs, and enhance system efficiency.

The device is designed with a user-friendly interface that simplifies setup and configuration. It features a web-based management platform that allows system integrators and technicians to configure settings, monitor system performance, and perform troubleshooting tasks remotely. This accessibility is particularly beneficial in minimizing downtime and ensuring that systems operate optimally.

FieldServer Technologies has also implemented advanced data logging capabilities within the FS-RA-CLX-BAS. Users can track real-time data trends, monitor system performance, and analyze historical data to make informed decisions. This feature is essential for identifying inefficiencies and enabling proactive maintenance, thus extending the lifespan of building systems.

The FS-RA-CLX-BAS is built with durability and reliability in mind, designed for use in demanding environments. Its compact design and robust construction allow for easy integration into existing setups without requiring extensive modifications. Additionally, with support for both wired and wireless communication methods, it offers flexibility in installation.

Beyond its core functions, the FS-RA-CLX-BAS is also equipped with security features to protect sensitive data being transmitted across networks. Encryption protocols help ensure that communications remain secure, mitigating risks associated with unauthorized access.

In summary, the FieldServer FS-RA-CLX-BAS stands out as a versatile and reliable solution for integrating various building automation systems. With its multi-protocol support, user-friendly interface, advanced data logging capabilities, and robust security measures, it empowers facility managers and system integrators to enhance operational efficiency while maintaining a high level of security and reliability. This makes it a key asset for modern building management and automation strategies.