MISCELLANEOUS SYSTEM FIELDS (*174-*181)

 

 

174

CLEAN ME REPORTING OPTIONS

[0]

 

 

(for ESL smoke detectors)

 

 

 

 

177

DEVICE DURATION 1, 2

 

[0] [0]

 

(used in *80 Menu mode-Device Actions 5/6)

 

 

1

2

 

 

181

50/60 HERTZ AC OPERATION

[0]

 

 

 

 

CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)

 

182

CONFIGURABLE ZONE TYPE 90

 

 

0 = disable; 1 = Clean Me signal reports;

Note: If Clean Me is enabled, you must enter “3” in field 56 programming for zone 1 response time.

0

= 15 seconds

6

= 2-1/2 min

#+11 = 7 min

1

= 30 seconds

7

= 3 min

#+12 = 8 min

2

= 45 seconds

8

= 4 min

#+13 = 10 min

3

= 60 seconds

9

= 5 min

#+14 = 12 min

4

= 90 seconds

#+10 = 6 min

#+15 = 15 min

5

= 2 minutes

 

 

 

0

= 60 Hz; 1 = 50 Hz

 

1 2 3 4 5 6 7 8 9 10

Enter the appropriate value for each entry, 1-10, based on the charts provided on the next page. Each entry is the sum of the values of its selected options

(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).

UL: Do not configure zones as a fire alarm or UL burglar alarm zone.

183 ZONE TYPE 90 REPORT CODES

IMPORTANT: Use existing Contact ID® codes, if appropriate, or define unique codes in CID code range 750-789. See important note in installation instructions.

90 ALARM ID: XXX TROUBLE ID: XXX

Enter the desired 3-digit Contact ID® report codes for alarms and troubles occurring on zones assigned to this zone type. Enter the codes sequentially (all 6 digits). When entering digits, [#] moves cursor back, [] moves forward. Press [] when done to continue.

184 CONFIGURABLE ZONE TYPE 91

185 ZONE TYPE 91 REPORT CODES

IMPORTANT: Use existing Contact ID® codes, if appropriate, or define unique codes in CID code range 750-789. See important note in installation instructions.

TOUCH SCREEN DEVICE (AUI) ENABLE

189 AUI DEVICE 1 and 2 ENABLE (for Touch Screen style keypads)

NOTE: System supports up to two touch screen style keypads (e.g. Symphony Advanced User Interface, and 6270 Touch Screen keypad).

1 2 3 4 5 6 7 8 9 10

Enter the appropriate value for each entry, 1-10, based on the charts provided on the next page. Each entry is the sum of the values of its selected options

(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).

UL: Do not configure zones as a fire alarm or UL burglar alarm zone.

 

91 ALARM ID: XXX

Enter the desired 3-digit Contact ID® report codes for

 

TROUBLE ID: XXX

alarms and troubles occurring on zones assigned to

 

 

 

 

 

this zone type. Enter the codes sequentially (all 6

 

 

 

 

 

 

 

 

 

 

digits). When entering digits, [#] moves cursor back, []

 

 

 

 

 

moves forward. Press [] when done to continue.

 

 

 

 

[1] [1]

Enter each touch screen (AUI) device’s home partition.

 

 

 

 

 

 

 

0

= disabled

AUI 1 AUI 2

1

= partition 1; 2 = partition 2; 3 = partition 3 (common)

AUI 1: Must set AUI address to 1

NOTE: A minimum of one standard keypad must also be

AUI 2: Must set AUI address to 2

installed when AUI is used. Use of AUI does not affect

(see Inst. Instr. for details)

the number of standard keypads supported.

KEYPAD OPTIONS *190-*196(NOTE: Options for keypad address 16 are set by the factory and cannot be changed.)

NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results.

190

KEYPAD 2 DEVICE ADDRESS 17

 

[0] [0]

Partition:

0 = keypad disabled; 1-3 = part. no. (3 = com)

 

 

 

Sound:

0 = no suppression

 

 

Partition/

Sound

 

 

 

1 = suppress arm/disarm and E/E beeps

 

 

Enable

 

 

2 = Suppress chime beeps only

 

 

†FA168CPS: enter partition

 

3 = suppress arm/disarm, E/E, and chime

 

 

FA148CP:

1 = enable

 

beeps

 

 

 

0 = disable

 

 

 

 

Part./Enable

Sound

See field 190 for entries.

191

KEYPAD 3 DEVICE ADDRESS 18

 

[0] [0]

 

 

 

 

 

192

KEYPAD 4 DEVICE ADDRESS 19

 

[0] [0]

See field 190 for entries.

 

 

 

 

 

193

KEYPAD 5 DEVICE ADDRESS 20

 

[0] [0]

See field 190 for entries.

 

 

 

 

 

194

KEYPAD 6 DEVICE ADDRESS 21

 

[0] [0]

See field 190 for entries.

 

 

 

 

 

195

KEYPAD 7 DEVICE ADDRESS 22

 

[0] [0]

See field 190 for entries.

 

 

 

 

 

196

KEYPAD 8 DEVICE ADDRESS 23

 

[0] [0]

See field 190 for entries.

 

 

 

 

 

197

EXIT TIME DISPLAY INTERVAL

[0]

 

0 = no display; 1-5 = seconds between display refresh

 

 

 

NOTE: If enabled and using only 2-digit fixed-word

 

 

 

 

 

 

 

 

keypads (e.g., FA245RF), do not set exit delay time

 

 

[0]

 

greater than 96 seconds. See Inst. Instr. for explanation.

198 DISPLAY PARTITION NUMBER

 

0 = no; 1 = yes (partition no. appears on Alpha Display)

 

(FA168CPS; for Alpha Display Keypads)

 

 

0 = 3-digit display (“1” + device address)

199

ECP FAIL DISPLAY

[0]

 

 

 

 

1 = 2-digit fixed-display as “91”

 

 

 

 

7

Page 7
Image 7