Fluke 2686A, 2680A manual Using Equations with Computed Channels

Models: 2686A 2680A

1 74
Download 74 pages 62.55 Kb
Page 59
Image 59

Getting Started

Managing Your Network Using Fluke DAQ

Using Equations with Computed Channels

Each computed channel can have an expression of 250 characters but the maximum number of characters available in all 60 channels is limited to 6,000 characters.

For example, you could use an equation to calculate the rate of flow in gallons per second. The rate of flow could be calculated as follows. Since TS is in milliseconds, you need to divide by 1000 to calculate gallons per second. In this example, during the first pass, C902 will not be defined and the result will be not a number (#Inf). However, in subsequent passes, C902 will be defined and will provide the correct result.

C101 = some fake measurement to force the time calculation

C901 = (TOT-C902)/(TS/1000)

C902 = TOT

Note

You need one physical channel configured in the module that you’re scanning for this to work even though you’re not using the channel in the expression.

Computed channels and the time value are initialized to zero at the beginning of scanning. Physical channels that haven’t been measured are still initialized to positive infinity.

To measure the total energy used by a simple system, a calculation could be generated using the equation, energy = R x I^2 * time, as follows:

c101 = Ohms

c102 = Current

c959 = c959+c960

c960 = c101*c102**2*ts/1000

Note

This equation assumes that the resistance and current are constant for the duration of the time interval. It also does not calculate the energy used in the first increment of time.

49

Page 59
Image 59
Fluke 2686A, 2680A manual Using Equations with Computed Channels