G VA Check Screen

VA Check Screen

Press Gat any time to access the VA Check screen, which displays volts graphed against amps. P ess Ga second time to exit the VA Check screen and return to your sta ting point.

provide a meaningfulfordisplay. If the Tester is set for manual ranging (MAN), both scales (ranges) a e fixed; you may have to choose AUTO (press rfor 1 second) or select an app opriate manual range in either V or A, or both

With the VA Check sc een, the Tester displays one cycle of the fundamental frequency (current on the vertical scale, voltage on the horizontal scale). The resulting graph can appear as a straight line, a stepped line, an ellipsoid, or as some other pattern that you would normally expect to see on an oscilloscope with two input channels.

Use the VA Check sc een to show the phase shift of the fundamental frequency and detect the existence and severity of nonlinearity caused by harmonics. It could be that the VA Check screen may simply show that you

have clamped the Cu

ent Probe in the wrong direction. Figure 15 shows

some typical VA Check signatures.

When the Tester is set

autoranging (AUTO), ranges for the vertical and

horizontal scales on the VA Check screen are adjusted automatically to

functions (i.e., press briefly for each range change).

Note

V or A ranges cannot be changed while in the VA Check screen.