Fluke 41B, 39 user manual Watts Measurements Volt-Amps, Harmonic Level 5% Using Smooth ~20

Models: 39 41B

1 74
Download 74 pages 42.42 Kb
Page 68
Image 68

39/41B

Users Manual

Watts Measurements (Volt-Amps)

(1 mV/A) Isolated Input

Range: 0 W (VA) to 600 kW (kVA) average 0 W (VA) to 2000 kW (kVA) peak

Accuracy (ac + dc):

Active W (VA): +/-(1% + 4 digits) + probe specs

Harmonics Measurement Accuracy (Cursor Data)

(Harmonic Level > 5% Using Smooth ~20)

Volts:

Fundamental to 13th Harmonic:

+/- (2% + 2 digits)

13th to 31st Harmonic:

13th (+/- (2% + 2 digits)) -----

 

----- 31st (+/- (8% + 2 digits))

Amps* or Watts:

Fundamental to 13th Harmonic:

+/- (3% + 3 digits) + probe specs

13th to 31st Harmonic:

13th (+/- (3% + 3 digits) + probe

 

specs) ---------- 31st (+/- (8% + 3

 

digits)+ probe specs)

* < 20A, add 3 digits

 

Phase:

Fundamental:

(±2 degrees) + probe specs

2nd to 31st Harmonic:

2nd (±5 degrees) -- 31st (±20

 

degrees) + probe specs

Frequency Measurement Accuracy

(Fundamental, 6.0 Hz - 99.9 Hz)

6.0 Hz - 99.9 Hz:+/- 0.3 Hz

58