Parameter Definitions
/2 Measurement stability.
Defines the coefficient used to stabilise the temperature reading.
/3 | Probe display rate |
| Sets the rate at which the temperature display is updated. |
/4 | Probe average (Virtual probe) |
| Used to choose whether to control the temperature based solely on the room probe reading, or |
| alternatively whether to refer to the average of the room probe S1 and probe 2(S2, see parameter /A2). |
/5 | Select °C or °F |
| Defines the unit of measure in degrees centigrade or Fahrenheit. |
/6 | Decimal point |
| Used to enable or disable the displaying of the temperature with the resolution to the tenth of a degree |
| between |
/tI | Probe displayed by instrument |
| Select the probe to be displayed by the instrument. |
| Warning: Control is always based on the virtual control probe. |
/tE | Probe displayed on external terminal |
| Selects the probe to be displayed on the remote terminal. |
/P | Select type of probe |
| Used to select the type of probe for temperature measurement. |
| Default. /P = standard NTC probe with range |
/A2 | Configuration of probe 2 |
| Used to configure the operating mode of probe 2. |
| Default: /A2 =2 = Defrost probe. |
/A3 | Configuration of probe 3 |
| Used to configure the operating mode of probe 3. |
| Default: /A3 = 0 = Probe 3 absent. |
/A4 | Configuration of probe 43 |
| Used to configure the operating mode of probe 43. |
| Default: /A4 = 0 = Probe 4 absent. |
/C1 | Calibration or offset probe 1 |
/C2 | Calibration or offset probe 2 |
/C3 | Calibration or offset probe 3 |
/C4 | Calibration or offset probe 4 |
| These parameters are used to correct the temperature by the probes using an offset. |
| Example: To decrease the temperature measured by probe 1 by 2.3 degrees, set /C1 = |
St | Set point |
| Establishes the controller set point. |
| Default: St = 0.0 |
rd | Control delta |
| Establishes the value of the differential, or hysteresis, used to control the temperature. |
| Default: rd = 2.0. Foster setting: rd = 4.0 |
r1 | Minimum allowed set point |
| Determine the set point minimum value. |
| Default: r1 = |
r2 | Maximum allowed set point. |
| Determine the set point maximum value. |
| Default: r2 = +60. Foster setting: r2= |
8