Friedrich 920-087-09 (12/10) PTAC Installation Recommendations, View Outside Building Elevation

Models: 920-087-09 (12/10)

1 36
Download 36 pages 5.9 Kb
Page 5
Image 5
PTAC Installation Recommendations

PTAC Installation Recommendations

For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances below:

Figure 1

PTAC units should be installed no closer than 12" apart when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units. Also, a vertical clearance of 60" should be maintained between units installed. In the interior of the room the unit should be located a minimum of 1/4" from the floor and a minimum of 36" from the ceiling.

60" VERTICAL MINIMUM BETWEEN PTACs

THREE OR MORE PTACs

ADJACENT 36" MINIMUM

TYPICAL

WINDOW

36"

60"

TWO ADJACENT PTACs

12" MINIMUM

 

 

GROUND FLOOR PTACs

 

6" MINIMUM FROM GRADE

12" 6"

VIEW: OUTSIDE BUILDING ELEVATION

FRP001

For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:

Figure 2

For minor obstr uc tions

 

such as lamp poles or small

 

shrubbery a clearance of

 

12" from the outdoor louver

 

should be maintained.

For major obstructions such

TYPICAL BUILDING ( PLAN VIEW )

as a solid fence, wall or

other heat rejecting device

like a condensing unit, a

minimum distance of 36"

should be kept.

 

36"

 

36"

PTAC

 

PTAC

 

 

 

12"

 

12" MINIMUM, MINOR

POLE

36"

SHRUB

OBSTRUCTIONS

 

 

 

36" MINIMUM, MAJOR

 

 

 

OBSTRUCTIONS

 

FENCE OR WALL

CONDENSING UNIT

PTAC

FRP002

The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich for information regarding affects of other installation arrangements. By following these simple recommendations you can be confident that your Friedrich PTAC will provide years of worry free operation.