Friedrich 920-087-09 (12/10) Wall Sleeve Installation Instructions PDXWS, Falling Object Hazard

Models: 920-087-09 (12/10)

1 36
Download 36 pages 5.9 Kb
Page 6
Image 6
Wall Sleeve Installation Instructions (PDXWS)

Wall Sleeve Installation Instructions (PDXWS)

NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely before attempting installation.

Falling Object HazardWARNING

Falling Object Hazard

Not following Installation Instructions for mounting your air conditioner can result in property damage, injury, or death.

NOTICE

DO NOT allow any pitch toward the inside.

Flashing on all 4 sides of the opening is recommended.

Potential property damage can occur if instructions are not followed.

For Deep Wall Installation (Greater than 13 1/4") See Page 9

The following instructions apply ONLY to walls less than 13 ¼" in depth.

1.The PXDR10 Drain Kit (optional for new construction) see page 10 if applicable, must be installed before the wall sleeve is installed into the wall.

2.The External Drain (for new construction or unit replacement) see page 11, if applicable, must be installed before the wall sleeve is installed into the wall.

Figure 3

Typical Wall Sleeve Installation

LINTEL TO SUPPORT

42-¼"

MIN.

MASONRY WALLS

 

3.From inside the building, position the wall sleeve in the opening and push it into the wall until it protrudes at least ¼” on the outside. Do not allow sleeve to be pulled. (See Figure 11, Page 10).

4.Position the wall sleeve with a slight tilt towards the outside to facilitate condensate drainage. It should be level side-to-side and the front should be ¼ bubble higher than the back.

ELECTRICAL

RECEPTACLE

16-¼"

 

 

60"

 

 

MAX.

 

20" MAX.

13-¾"

SMOOTH SIDE OF SCREW CLIP FACING INTO ROOM

ELECTRICAL

INSULATION

RECEPTACLE

WALL OPENING

WALL SLEEVE

INSULATION

NOTE: All 230/208V units are manufactured with a 72” power cord and all 265V units with a 20” power cord.

FRP008

6

Page 6
Image 6
Friedrich 920-087-09 (12/10) operation manual Wall Sleeve Installation Instructions PDXWS, Falling Object Hazard