Appendix A (continued)

920-087-02 (9-03)

Appendix A (continued)

Remote Thermostat 208V Operation

Connection Diagram

208V 60HZ

L2 Remote Thermostat 208V OperationConnection Diagram208V 60HZL1

SMOOTH G RIBBED

 

SECONDARY TRANSFORMER PRIMARY

240V

 

Y

24V

 

208V

COM

RED

R

BK

Auto Changeover Thermostat

A single stage heat/cool thermostat with auto changeover is needed. The wiring scheme is the same as the manual thermostat.

Remote Thermostat Installation

Follow Steps 1 through 5 (pages 12 and 13), then:

6.Locate the terminal strip on the front of the control box (See Figure 9). Attach the thermostat subbase wires (field supplied) to the appropriately labeled terminals in accordance with the wiring diagram on the side of the chassis.

7.Carefully route the wires alongside the conduit or service cord. Attach the other end of the wires to the appropriate terminals on the thermostat subbase. See the thermostat directions for proper wiring and mounting of the thermostat.

The simplified connection diagram at left shows the factory configured wiring set for 240V operation. If you are going to use 208V exclusively, switch the two (2) black wires on the 240V post of the primary side of the transformer to the 208V post. This will ensure correct secondary (low) voltages for the unit. This is only required on remote thermostat units.

CAUTION

If the supply voltage is 208V, the low voltage transformer MUST be wired for 208V operation. Failure to do so will result in lower control voltages to the unit and can damage low voltage components.

Remote Thermostat Unit Operation

These units are controlled by the use of a remote thermostat that will cycle the unit to maintain desired room temperature. See thermostat operating instruction sheet for details.

The fan speed switch controls high and low speed fan operation. It is located on the control panel and is independent of the thermostat.

Figure 10

 

 

Terminal Strip Location

 

 

Remote

Contr

 

 

 

 

ol

Unit

 

OFF

 

ON

 

C W Y R G B

 

 

18

Page 18
Image 18
Friedrich PTAC Appendix A continued, Remote Thermostat 208V Operation, Auto Changeover Thermostat, Terminal Strip Location