H. Air Discharge Grille

920-087-02 (9-03)

H. Air Discharge Grille

Moving parts hazard.

Turn off electric power before servicing this component.

Failure to do so can result in property damage, personal injury and/or death.

The air discharge grille can be redirected to blow air either straight up or at an angle into the room. To change the airflow direction, remove the front cover, locate and remove the six grill retaining screws. Reverse the ends of the grille and refasten the grille to the cover.

I. Start-up Checklist

oInspect all components and accessories for damage before and after installation.

oCheck installation for compliance with all national and local codes and ordinances.

oRead and follow all manufacturer's installation instructions.

oCheck that circuit breaker(s) and electrical wire sizes are correct. If the unit is supplied with a power supply cord, insure that it is stored properly.

oCheck the condensate water drain outlet(s) to make sure they are in compliance with all national and local codes, that they are adequate for the removal of condensate water, and that they meet the approval of the end user.

oStrictly follow installation instructions concerning clearances around the unit.

oSecure components and accessories, such as the control door and front cover.

oCheck the unit air filter, condenser coil and evaporator coil for any obstructions.

oCheck for proper operation of all components.

oInstruct the owner or operator of the units operation, and the manufacturer's

recommended routine maintenance schedule.

NOTE: It is highly recommended that a maintenance schedule log book be prepared for recording the dates and times of service.

oOperate the unit for twenty minutes. Record the unit's indoor/outdoor intake and discharge temperatures, amperage draw, and power voltage.

oAssemble the Warranty Certificate, the Operation and Installation Manual, all accessory installation instructions and the name, address and telephone number of the Authorized Friedrich Warranty Service Company in the area for the owner or operator.

NOTE: Units are to be installed, inspected, and checked by qualified service personnel only.