TROUBLESHOOTING
Problem | Possible Cause | Possible Solution | |
| Compressor attempts to start | Allow a minimum of 3 minutes to allow pressures | |
| before system pressures are | ||
| to equalize before attempting to start. | ||
| equalized. | ||
|
| ||
|
| Check voltage with unit operating. Check for | |
| Low or fluctuating voltage. | other appliances on the circuit. Unit should be on | |
| separate circuit for proper voltage, and be fused | ||
Compressor |
| ||
| separately | ||
attempts to |
|
| |
Incorrect wiring | Connect per appropriate wiring diagram | ||
start, or runs for | |||
Shorted or incorrect capacitor | Replace capacitor | ||
short periods | |||
only. Cycles on |
|
| |
Restricted or low air flow through |
| ||
overload. | Check motor fan blade. | ||
condenser coil | |||
|
| ||
| Compressor running abnormally | Check for refrigerant restriction, blocked airflow, | |
| loose wires at compressor terminals and fan | ||
| hot | ||
| motor capacitor voltage. | ||
|
| ||
| Overload opens too soon. | Change compressor if all other corrections above | |
| are normal. | ||
|
|
Problem | Possible Cause | Possible Solution |
| Thermostat contacts not closing. | Check continuity of thermostat at coldest setting. If |
| compressor runs, replace thermostat. | |
|
| |
| Low voltage supply. | Check for nameplate voltage. Provide proper |
| voltage. | |
|
| |
Compressor does | Switch | Test for continuity. |
not start - fan | Defective capacitor. | Test with analyzer, replace if needed. |
motor runs. | Compressor internal overload | Check voltage at compressor terminals. If voltage |
| open. | is satisfactory, replace compressor. |
| Solid state relay open. | Replace relay. |
| Open or shorted compressor | Check windings for continuity and resistance. If |
| windings. | open, replace compressor. |
Problem | Possible Cause | Possible Solution | |
|
|
| |
| Thermostat open or inoperative. | Set to coldest position. Test thermostat and | |
| replace if necessary. | ||
|
| ||
| Dirty air filter. | Clean as recommended in Owner’s Manual. | |
|
|
| |
Does not cool, or | Dirty or plugged condenser or | Clean coils. | |
evaporator coil. | |||
| |||
cools only slightly. |
|
| |
Poor air circulation in area being | Adjust air louvers. Check application. Check for | ||
| |||
| dirty filter or evap coil. Check fan motor. Correct as | ||
| cooled. | ||
| needed. | ||
|
| ||
| Low capacity - undercharge. | Check for leak and make necessary repairs. | |
|
|
| |
|
|
| |
| Compressor not pumping properly. | Replace compressor. | |
|
|
|
NOTE: If Inside Coil Freezes Up
Your Friedrich Hazardgard is designed not to freeze with outdoor temperatures as low as 45°F (7°C). If the indoor coil should ice over while cooling, set the thermostat to the warmest position until the ice on the coil is gone. Setting the thermostat to a slightly warmer position will probably keep ice from forming on the coil. A dirty filter will contribute to icing.
25