Friedrich R-410A Heating Load Form Friedrich Room Unit Heat Pumps, WINDOWS & DOORS Area, sq. ft

Models: R-410A

1 47
Download 47 pages 33.75 Kb
Page 43
Image 43
HEATING LOAD FORM

HEATING LOAD FORM

FRIEDRICH ROOM UNIT HEAT PUMPS

WALLS: (Linear Feet)

BTU/HR PER

°F TEMP. DIFFERENCE

2” Insulation

Lin. Ft. x 1.6

Average

Lin. Ft. x 2.6

WINDOWS & DOORS (Area, sq. ft.)

 

Single Glass:

Sq. Ft. x 1.13

Double Glass:

Sq. Ft. x 0.61

INFILTRATION - WINDOWS & DOORS: AVG.

Lin. Ft. x 1.0

Loose

Lin. Ft. x 2.0

CEILING: (Area, Sq. Ft.)

 

Insulated (6”)

Sq. Ft. x 0.07

Insulated (2”)

Sq. Ft. x 0.10

Built-up Roof (2” insulated

Sq. Ft. x 0.10

Built-up Roof (1/2” insulated)

Sq. Ft. x 0.20

No Insulation

Sq. Ft. x 0.33

FLOOR: (Area, Sq. Ft.)

 

Above Vented Crawl space

 

Insulated (1:)

Sq. Ft. x 0.20

Uninsulated

Sq. Ft. x 0.50

* Slab on Ground

Lin. Ft. x 1.70

1” Perimeter insulation

Lin. Ft. x 1.00

* Based on Linear Feet of outside wall

TOTAL HEAT LOSS PER °F BTU/HR/°F

Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F. Draw a straight line from the 70 base point thru the point plotted at 40°F. The intersection of this heat loss line with the unit capacity line represents the winter design heating load.

7

42

Page 43
Image 43
Friedrich R-410A service manual Heating Load Form Friedrich Room Unit Heat Pumps, WINDOWS & DOORS Area, sq. ft