2.4.3 CAPILLARY TUBE

1.Remove the cabinet. (Refer to section 2.1.2)

2.After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.(See caution on previous page)

NOTES

3.Remove the capillary tube.

4.Re-install the components by referring to notes.

ÑReplacement of the refrigeration cycle.

1.When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System.

If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Remove the valve when finished.

2.After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with Service valves.

5.Evacuate as follows.

1)Connect the vacuum pump, as illustrated figure 16A.

2)Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.

CAUTION

If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

3)Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

4)Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 16B.

Open valve C.

Discharge the line at the manifold connection.

5)The system is now ready for final charging.

6.Recharge as follows :

1)Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

2)Connect the charging cylinder as shown in figure 16B.

With valve C open, discharge the hose at the manifold connection.

3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.

4)If more charge is required, the high-side will not take it. Close valve A.

5)With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the Low- side.

b.Watch the Low-side gauge; allow pressure to rise to 30 lbs.

c.Turn off valve B and allow pressure to drop.

d.Repeat steps b. and c. until the balance of the charge is in the system.

6)When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

Ñ11Ñ

Page 11
Image 11
Friedrich ZQ10B10, ZQ08B10, CP10A10, CP08A10, CP12A10 manual Capillary Tube

CP12A10, CP08A10, CP10A10, ZQ10B10, ZQ08B10 specifications

The Friedrich ZQ08B10, CP12A10, ZQ10B10, CP10A10, and CP08A10 represent a series of highly efficient and innovative units designed for heating and cooling applications. These systems are tailored to meet various environmental and operational demands, making them ideal for both residential and commercial sectors.

One of the main features of the Friedrich ZQ series is their energy efficiency. Equipped with advanced inverter technology, these units adjust their cooling and heating output based on the room's temperature, consuming less energy and reducing utility bills. This feature not only promotes a greener environment but also enhances users' comfort with consistent temperature control.

The ZQ08B10 and ZQ10B10 units excel in their cooling and heating capacities, making them suitable for varying room sizes. With a strong focus on versatility, these units can be installed in different configurations, including wall-mounted or ceiling-integrated systems, allowing for effective integration into existing spaces.

Another key characteristic is the quiet operation of these models. Friedrich has engineered its compressors and fans to minimize noise levels, providing a serene indoor environment. This is particularly beneficial for settings where noise can be a distraction, such as schools, offices, or residential bedrooms.

The CP series, which includes the CP08A10, CP10A10, and CP12A10, is celebrated for its smart technology features. These models come equipped with Wi-Fi connectivity, enabling users to control settings remotely via smartphone applications. This feature adds convenience and enhances energy management, allowing users to schedule operations and monitor energy consumption from anywhere at any time.

Additionally, the CP units include enhanced filtration systems designed to improve indoor air quality. Their multi-stage filters capture dust, allergens, and airborne particles, promoting a healthier living environment. This is a critical factor for households with allergy sufferers or individuals with respiratory issues.

Overall, the Friedrich ZQ08B10, CP12A10, ZQ10B10, CP10A10, and CP08A10 models stand out due to their energy efficiency, quiet operation, and smart technology features. They embody the perfect blend of performance, comfort, and advanced features, making them a valuable consideration for consumers looking for reliable heating and cooling solutions. As technology continues to evolve, these units maintain a strong position by adapting to user needs, ensuring lasting satisfaction and sustainability.