Friedrich CP08A10, ZQ08B10, ZQ10B10, CP10A10 manual Complaint, Cause, Remedy, Compressor will not run

Models: CP12A10 CP08A10 CP10A10 ZQ10B10 ZQ08B10

1 28
Download 28 pages 43.89 Kb
Page 18
Image 18

COMPLAINT

CAUSE

REMEDY

 

 

 

 

Compressor will not run,

Thermostat

Check the position of knob. If not at the coldest

but fan motor runs.

 

setting, advance the knob to this setting and restart

 

 

 

unit.

 

 

 

Check continuity of the thermostat. Replace

 

 

 

thermostat if circuit is open.

 

 

 

 

 

 

Capacitor (Discharge

Check the capacitor.

 

 

capacitor before servicing.)

Replace if not within ±10% of manufacturers rating.

 

 

 

Replace if shorted, open, or damaged.

 

 

 

 

 

 

Compressor

Check the compressor for open circuit or ground. If

 

 

 

open or grounded, replace the compressor.

 

 

 

 

 

 

Overload

Check the compressor overload, if externally

 

 

 

mounted. Replace if open. (If the compressor

 

 

 

temperature is high, remove the overload, cool it,

 

 

 

and retest.)

 

 

 

 

Compressor cycles on

Voltage

Check the voltage.

overload.

 

If not within limits, call an electrician.

 

 

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

 

Replace if open. (If the compressor temperature is

 

 

 

high, remove the overload, cool, and retest.)

 

 

 

 

Compressor cycles on

Fan motor

If not running, determine the cause. Replace if

overload.

 

required.

 

 

 

 

 

 

Condenser air flow

Remove the cabinet. inspect the interior surface of

 

 

restriction

the condenser; if restricted, clean carefully with a

 

 

 

vacuum cleaner (do not damage fins) or brush.

 

 

 

Clean the interior base before reassembling.

 

 

 

 

 

 

Condenser fins (damaged)

If condenser fins are closed over a large area on the

 

 

 

coil surface, head pressures will increase, causing

 

 

 

the compressor to overload. Straighten the fins or

 

 

 

replace the coil.

 

 

 

 

Compressor cycles on

Capacitor

Test capacitor.

 

 

overload.

Wiring

Check the terminals. If loose, repair or replace.

 

 

 

 

 

 

Refrigerating system

Check the system for a restriction.

 

 

 

Insufficient cooling or

Air filter

If restricted, clean of replace.

heating

 

 

Exhaust damper door

Close if open.

 

 

 

 

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the area to

 

 

 

be cooled.

 

 

 

Excessive noise

Blower or fan

Check the set screw or clamp. If loose or missing,

 

 

 

correct. If the blower or fan is hitting air guide,

 

 

 

rearrange the air handling parts.

 

 

 

 

 

 

Copper tubing

Remove the cabinet carefully and rearrange tubing

 

 

 

not to contact cabinet, compressor, shroud, and

 

 

 

barrier.

 

 

 

 