COMPLAINT

CAUSE

REMEDY

 

 

 

Fan motor noise.

Fan

If cracked, out of balance, or partially missing,

 

 

replace it.

 

 

 

 

Blower

If cracked, out of balance, or partially missing,

 

 

replace it.

 

 

 

 

Loose set screw

Tighten it.

 

 

 

 

Worn bearings

If knocking sounds continue when running or loose,

 

 

replace the motor. If the motor hums or noise

 

 

appears to be internal while running, replace motor.

 

 

 

Compressor will not run,

Voltage

Check voltage. See the limits on the preceding page.

fan motor runs.

 

If not within limits, call an electrician.

 

 

 

 

Wiring

Check the wire connections ; if loose, repair or

 

 

replace the terminal. If the wires are disconnected,

 

 

refer to wiring diagram for identification, and replace

 

 

the wires. Check the wire connections ; if not

 

 

according to the wiring diagram, correct the

 

 

connections.

 

 

 

 

Rotary

Check for continuity, refer to the wiring diagram for

 

 

terminal identification. Replace the switch if the

 

 

circuit is open.

 

 

 

 

Thermostat

Check the position of knob. If not at the coldest

 

 

setting, advance the knob to this setting and restart

 

 

the unit.

 

 

 

 

 

Check the continuity of the thermostat. Replace the

 

 

thermostat if the circuit is open.

 

 

 

 

Capacitor (Discharge

Check the capacitor.

 

capacitor before

Replace if not within ±10% of manufacturer's rating,

 

servicing.)

replace if shorted, open, or damaged.

 

 

 

 

Compressor

Check the compressor for open circuit or graond. If

 

 

open or grounded, replace the compressor.

 

 

 

 

Overload

Check the compressor overload if externally

 

 

mounted.

 

 

Replace if open. (If the compressor temperature is

 

 

high, remove the overload, cool and retest.)

 

 

 

Compressor cycles on

Voltage

Check the voltage. See the limits on the preceding

overload.

 

page. If voltage is not within these limits, call an

 

 

electrician.

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

Replace if open. (If the compressor temperature is

 

 

high, remove the overload, cool, and retest.)

 

 

 