Gaggenau AW 230 790 manual Safety clearances, General notes Exhaust air mode, Ventilation line

Models: AW 230 790

1 64
Download 64 pages 13.24 Kb
Page 17
Image 17
Safety clearances

Safety clearances

9WARNING

Risk of fire

Grease deposits in the grease filter may catch fire. The specified safety distances must be observed in order to prevent an accumulation of heat. Observe the specifications for your cooking appliance. If gas and electric cooktops are operated together, the largest specified distance applies.

Only one side of the appliance may be installed directly next to a high-sided unit or a wall. The distance between the appliance and wall or high-sided unit must be at least 2" (50 mm).

The minimum distance between the supporting surface for the cooking equipment on the hob and the lowest part of the range hood must be not less than 30 " (760 mm) from electric cookers and 30 "

(760 mm) from gas or mixed cookers.

If the instructions for installation for the gas hob specify a greater distance, this must be adhered to.

General notes

Exhaust air mode

9WARNING

Risk of death

Risk of poisoning from flue gases that are drawn back in. The exhaust air must not be conveyed into a functioning smoke or exhaust gas flue or into a shaft that is used to ventilate installation rooms that contain heating appliances. If the exhaust air is to be conveyed into a non-functioning smoke or exhaust gas flue, you must obtain the consent of the heating engineer responsible.

If the exhaust air is conveyed through the outer wall, a telescopic wall box should be used.

Ventilation line

Note: The manufacturer does not assume any warranty for complaints attributable to the pipe section.

The device achieves its optimum performance by means of a short, straight exhaust air pipe and as large a pipe diameter as possible.

The optimum extraction performance is not achieved and fan noise is increased if exhaust air pipes are long and rough and if there is a large number of pipe bends or diameters less than 5 15/ 16” (150 mm).

The pipes or hoses for laying the exhaust air line must consist of non-combustible material.

Round pipes

An inner diameter of 5 15/16” (150 mm), but at least 4 3/ 4” (120 mm), is recommended.

Flat ducts

The inner cross-section must correspond to the diameter of the round pipes.

Ø5 15/16” (150 mm) approx. 27 ½ sq in (177 cm2)

Ø4 3/4” (120 mm) approx. 17 ½ sq in (113 cm2)

Flat ducts should have no sharp deflections.

Use sealing strip for deviating pipe diameters.

17

Page 17
Image 17
Gaggenau AW 230 790 Safety clearances, General notes Exhaust air mode, Ventilation line, WARNING Risk of death, Flat ducts