CS300
2.5.3 External AC Mains Fuses
Converter | Ref. | Pieces | Europe |
|
|
| USA |
|
|
|
|
|
|
| |||
Type | Code | Type |
| Code | ||||
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
A | 3 | S00üF1/80/200A/660V | SKF4G23 |
| FWP200A | PDFP7V200ABLADE | ||
|
|
|
|
|
|
|
| |
B | 1+1 | S1üF1/110/250A/660V | SKF4G28 |
| FWP300A | PDFP7V300ABLADE | ||
|
| |||||||
|
|
|
|
|
|
|
|
|
A | 3 | S1üF1/110/315A/660V | SKF4G30 |
| FWP350A | PDFP7V350ABLADE | ||
|
|
|
|
|
|
|
| |
B | 1+1 | S1üF1/110/315A/660V | SKF4G30 |
| FWP350A | PDFP7V350ABLADE | ||
|
| |||||||
|
|
|
|
|
|
|
|
|
A | 3 | S2üF1/110/500A/660V | SKF4E30 |
| FWP500A | PDFP7V500ABLADE | ||
|
|
|
|
|
|
|
| |
B | 1+1 | S2üF1/110/500A/660V | SKF4E30 |
| FWP500A | PDFP7V500ABLADE | ||
|
| |||||||
|
|
|
|
|
|
|
|
|
A | 3 | S2üF1/110/630A/660V | SKF4E31 |
| FWP600A | PDFP7V600ABLADE | ||
|
|
|
|
|
|
|
| |
B | 1+1 | S3üF1/110/800A/660V | SKF4H02 |
| FWP800A | PDFP7V800ABLADE | ||
|
| |||||||
|
|
|
|
|
|
|
| |
A (1) | 3 | 170M5466 (1000A/700V) | SKS827B | 170M5466 (1000A/700V) | SKS827B | |||
B (1) | 3 | S2üF1/110/630A/660V | SKF4E31 |
| FWP600A | PDFP7V600ABLADE | ||
|
| |||||||
| A (1) | 3 | G3MUEF1/1000A/660V | SKF4G76 | G3MUEF1/1000A/660V | SKF4G76 | ||
|
|
|
|
|
|
|
| |
B (1) | (1+1)+ | S3üF1/110/1000A/660V | SKF4H03 | A70P1000 |
| FWP1000 | SKS7812 | |
|
| |||||||
|
| (1+1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| cs041 |
Ref: A: External fuses for the input side power supply bridge
B:External fuses for the DC link output (1): Fuses integrated in the device
Fuse manufactures: S… , G… | Jean Muller, Eltville |
A70… | Ferraz Shawmutt |
FWP…, 170M.. | Bussmann |
2.5.4 AC Mains Choke
| Main |
| Main |
| ||
Converter | frequency | Rated inductance | Rated AC | Saturation |
| Type |
| [Hz] | [mH] | current [A] | current [A] |
| |
|
|
| ||||
50/60 | 0.148 | 173 | 350 |
|
| |
50/60 | 0.082 | 360 | 540 |
| KLR 420 CCB | |
50/60 | 0.082 | 360 | 540 |
| KLR 420 CCB | |
50/60 | 0.053 | 560 | 840 |
| KLR 600 CCB | |
50/60 | 0.033 | 900 | 1350 |
| KLR 950 CCB | |
50/60 | 0.019 | 1425 | 2138 |
|
|
cs050
NOTE!The use of AC mains choke on the power supply input is MANDATORY
13 |