2.6.2 Drive DC Current (DC Link Circuit)

Rated motor

Motor

Current

Current

Fuses

AV300 -…

power

efficiency

Dclink IDCL

DClink IDCL

DClink

 

 

 

PMot

Mot

Continuous class 1

Overload class 2

Superfast

class 1

 

class 2

 

[kW]

 

[A]

[A]

[A]

 

 

 

0,55

0,71

1,56

2,12

6

4003

 

4003

0,75

0,74

2,04

2,77

6

4003

 

4003

1,1

0,75

2,95

4,01

6

4003

 

4003

1,5

0,75

4,02

5,47

8

4003

 

4003

2,2

0,79

5,60

7,61

10

4003

 

4003

3

0,81

7,44

10,12

16

4003

 

4003

4

0,83

9,68

13,17

16

4005

 

4005

5,5

0,84

13,16

17,90

20

4005

 

4007

7,5

0,86

17,53

23,83

30

4007

 

4011

11

0,88

25,12

34,16

40

4011

 

4015

15

0,89

33,87

46,06

63

4015

 

4022

18,5

0,905

41,08

55,87

63

4022

 

4022

22

0,912

48,48

65,93

80

4022

 

4030

30

0,918

65,67

89,32

100

4030

 

4037

37

0,923

80,56

109,56

125

4037

 

4045

45

0,93

97,24

132,25

160

4045

 

4055

55

0,935

118,21

160,77

200

4055

 

4075

75

0,943

159,83

217,37

250

4075

 

4090

90

0,946

191,19

260,02

315

4090

 

4110

110

0,947

233,43

317,46

350

4110

 

4132

132

0,951

278,94

379,35

450

4132

 

4160

160

0,955

336,69

457,90

500

4160

 

4250

200

0,958

419,54

570,58

630

4250

 

4250

250

0,96

523,33

711,74

800

4250

 

4315

315

0,963

657,35

893,99

1000

4315

 

 

355

0,963

740,82

1007,52

 

 

 

 

400

0,965

833,00

1132,88

 

 

 

 

cs070

The following table states the direct current values of the dc-link according to the rated power of the motor connected to the inverter The current is calculated on the basis of the following:

-4-pole “standard” motor

-“typical” efficiency for “standard” motors (η Mot)

-the “typical” inverter efficiency is considered equal to 0.97 (η I)

-mains power supply voltage 3 x 380V (conservative value if referred to a rated voltage of 3 x 400V)

-there are two value columns referring to a continuous functioning (class 1) or to a functioning during an overload phase (class 2) (150% for 60 seconds).

The current value in column 1 is calculated as

IDCL = PMot / (hMot x hI x ULN x 1.35)

where for column „Current Dclink IDCL Overload class 2“ it is obtained multiplying by 1.36.