![](/images/new-backgrounds/1192168/192168215x1.webp)
7 |
Forcing an Analog Circuit
If the circuit to be forced is an analog circuit, its current value appears on line 3 of the Monitor screen.
MNTR3 143#0.3 %AI 1 STS ±22138
> ref force diag
Pressing F3 (force) displays:
a Circuit value
MNTR3 143#0.3 %AI 1 FRC ±22138
> ref force diag
Circuit is
anot forced
Press F2 (force) to enter a forced value for the circuit. The screen displays:
FORCE TO: ______
chng entr
Press F2 (chng). Enter the value, then press F3 (entr). The forced value appears on line 3.
MNTR3 143#0.3 %AI 1 STS ±10000 FRC
force release
a Circuit is forced
To release the force, press F4 (release) from the force/release screen.
Chapter 7 Remote Drop I/O Data | 105 |