GE GFK0579B user manual IO 32IN IO 16IN

Models: GFK0579B

1 154
Download 154 pages 8.79 Kb
Page 89
Image 89

6

When configured with a Hand±held Monitor, the Remote I/O Scanner automatically assigns I/O references to the modules in the remote drop starting with the reference(s) assigned by the user via the Program Block ID screens. The left±most module of each type (%I, %Q, %AI, or %AQ) in the rack receives the first available reference of the appropriate type. The HHM then incrementally assigns references according to the types and locations of modules in the rack, in left±to±right order.

Example

For this remote drop, %I, %Q, %AI, and %AQ references each begin at 0001. There is no requirement that they all start at the same value.

Rack 0

 

Left

' reference values increase ' Right

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PS

Scanner

IO 32IN

IO 16IN

IO 32OUT

IO 32IN

IO 16OUT

IO 8AIN

IO 8AIN

IO 4AOUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32±ckt discrete input module: %I0001±%I0032

16±ckt discrete input module: %I0033±%I0048 32±ckt discrete output module: %Q0001±%Q0032

32±ckt discrete input module: %I0049±%I0080 16±ckt discrete output module: %Q0033±%Q0048 8±channel analog input module: %AI0001±%AI0008 8±channel analog input module: %AI0009±%AI0016 4±channel analog output module: %AQ0001±%AQ0004

Chapter 6 Remote Drop Configuration with a Hand±held Monitor

85

Page 89
Image 89
GE GFK0579B user manual IO 32IN IO 16IN