Display and Clear Faults from Logicmaster 5 or Logicmaster 6

If the host CPU is a Series Five or Series Six PLC, faults from a remote drop are displayed in the Genius Fault Table. A Logicmaster 6 fault table is illustrated below. The Logicmaster 5 fault table is similar.

Faults from remote drops are identified as GENA faults. The GENA is the component within the Remote I/O Scanner that handles the Genius bus interface.

 

 

 

 

 

 

L/M: OFFLINE

 

TOTAL FAULTS: 0000

GENIUS I/O FAULT TABLE

date

 

TOP FAULT DISPLAYED:0000

 

 

time

 

FAULT DISPLAYED:

 

 

0000:00:00:00:0

B/C

POINT

CIRC

FAULT

FAULT

FAULT

 

ADDR.

ADDR.

NO.

CATEGORY

TYPE

DESCRIPTION

DAY:HR:MN:SC:T

±±±±±

±±±±±± ±±±± ±±±±±±±±±±±±±±±± ±±±±±±±± ±±±±±±±±±±È±±±±± ±±±±±±±±±±±±±±±

0

0

I0001

1

CIRCUIT FAULT

DISCRETE

OPEN WIRE

147:12:03:12:44

0

64

O0053

6

CIRCUIT FAULT

DISCRETE

NO LOAD

147:13:56:31:04

1

32

IO001

 

 

GENA

 

148:03:12:48:55

NEXT

1 PAGE

PREV

2 PAGE

CLEAR

3FAULTS 4 TOP

5BOTTOM 6

7

XPNDED

8 FUNC

Fault Clearing

Pressing the Clear Faults key clears all faults currently in the fault table. This sets the fault count to zero, and sends a Clear command to the Remote I/O Scanner.

Chapter 8 Diagnostics and Fault Clearing

121