8 |
Display and Clear Faults from Logicmaster 5 or Logicmaster 6
If the host CPU is a Series Five or Series Six PLC, faults from a remote drop are displayed in the Genius Fault Table. A Logicmaster 6 fault table is illustrated below. The Logicmaster 5 fault table is similar.
Faults from remote drops are identified as GENA faults. The GENA is the component within the Remote I/O Scanner that handles the Genius bus interface.
|
|
|
|
|
| L/M: OFFLINE | |
| TOTAL FAULTS: 0000 | GENIUS I/O FAULT TABLE | date | ||||
| TOP FAULT DISPLAYED:0000 |
|
| time | |||
| FAULT DISPLAYED: |
|
| 0000:00:00:00:0 | |||
B/C | POINT | CIRC | FAULT | FAULT | FAULT |
| |
ADDR. | ADDR. | NO. | CATEGORY | TYPE | DESCRIPTION | DAY:HR:MN:SC:T | |
±±±±± | ±±±±±± ±±±± ±±±±±±±±±±±±±±±± ±±±±±±±± ±±±±±±±±±±È±±±±± ±±±±±±±±±±±±±±± | ||||||
0 | 0 | I0001 | 1 | CIRCUIT FAULT | DISCRETE | OPEN WIRE | 147:12:03:12:44 |
0 | 64 | O0053 | 6 | CIRCUIT FAULT | DISCRETE | NO LOAD | 147:13:56:31:04 |
1 | 32 | IO001 |
|
| GENA |
| 148:03:12:48:55 |
NEXT |
1 PAGE |
PREV |
2 PAGE |
CLEAR |
3FAULTS 4 TOP |
5BOTTOM 6
7
XPNDED |
8 FUNC |
Fault Clearing
Pressing the Clear Faults key clears all faults currently in the fault table. This sets the fault count to zero, and sends a Clear command to the Remote I/O Scanner.
Chapter 8 Diagnostics and Fault Clearing | 121 |