Use FTP or SCP to upgrade multiple Rack PDUs. To upgra de multiple
Switched Rack PDUs using an FTP client or using SCP, write a script which
automatically performs the procedure. For FTP, use the steps in Use FTP or
SCP to upgrade one Rack PDU.
Use XMODEM to upgrade one Rack PDU
To use XMODEM to upgrade the firmware for a single Switched Rack PDU
that is not on the network:
1. Obtain the individual firmware modules (the AOS module and the
application module) from the support section of the APC web site
www.apc.com/tools/download.
See also
See Release Notes: ini File Utility, version 1.0
(.\doc\en\ininotes.pdf) on the APC Rack PDU Utility CD that
came with your Rack PDU.
You cannot upgrade the AOS firmware module of any APC device
directly from firmware version 1.x.x to 2.1.0 or later. The upgrade
attempt will fail.
To upgrade the AOS firmware module of an APC device from
version 1.x.x to 2.1.0 or later, first upgrade the module to the latest
available version 2.0.x AOS firmware module. Then upgrade it
again, this time from version 2.0.x to the 2.x.x version you want.
If your APC device is running a 2.0.x of the AOS firmware module
already, you can upgrade directly to version 2.1.0 or a later
version.