Switched Rack PDU

USER’S GUIDE

®

Local access to the control console

You can use a local computer that connects to the Rack PDU through the serial port on the front panel of the unit.

1.Select a serial port at the local computer, and disable any service which uses that port.

2.Use the supplied serial cable (940-0144) to connect the selected port to the serial port on the front panel of the Rack PDU.

3.Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.

4.Press ENTER, repeatedly if necessary, to display the User Name prompt.

17

Page 20
Image 20
APC AP7900 manual Local access to the control console